18 AWG Wire

18 AWG (American Wire Gauge) wire specifications: 1.0237 mm diameter, 0.823 mm² area, 14A ampacity (copper, 90°C column only). Resistance, weight, and common uses.

Diameter
1.0237 mm
0.040303"
Area
0.823 mm²
1,624 cmil
Ampacity (Cu)
14A
90°C · NEC 310.16
Resistance (Cu)
20.9466
Ω/km at 20°C

18 AWG — Complete Specifications

Diameter1.0237 mm · 0.040303" · 40.3 mils
Cross-sectional area0.823 mm² · 1,624 circular mils
Resistance (copper, 20°C)20.9466 Ω/km · 6.3845 Ω/1000ft
Resistance (aluminum, 20°C)34.3388 Ω/km · 10.4665 Ω/1000ft
Ampacity — copper 60°C— A
Ampacity — copper 75°C— A
Ampacity — copper 90°C14 A
Flexible cord (NEC Table 400.5(A)(1))10 A (2 conductors) · 7 A (3 conductors)
Ampacity — aluminum 75°C— A
Weight (copper)7.374 kg/km · 4.955 lbs/1000ft
Weight (aluminum)2.222 kg/km · 1.493 lbs/1000ft
Closest IEC 60228 size0.75 mm²
Skin depth at 60 Hz8.531 mm

Common Uses for 18 AWG Wire

Compatible Insulation Types

TypeTemperatureDescription
TFFN/TFN 90°C Fixture wire
SPT-2 60–105°C Lamp and zip cord
SJT/SJOOW 60–105°C Portable and extension cord
MTW 60/90°C Machine tool wire

Frequently Asked Questions

What is 18 AWG wire used for?

18 AWG copper is used for lamp cords, fixture wires, thermostats and control circuits. It is too small for general-purpose branch circuits, which require at least 14 AWG copper. Diameter is 1.024 mm and cross-section 0.823 mm².

What is the ampacity of 18 AWG wire?

NEC Table 310.16 lists 18 AWG only in the 90°C column, at 14A. As flexible cord, NEC Table 400.5(A)(1) rates it 10A with two current-carrying conductors or 7A with three. NEC 240.4(D) permits 18 AWG on 7A overcurrent protection only in specific cases such as listed fixture wire and cords.