Wire Types

The insulation type printed on a conductor decides three things: how hot it may run, whether it may get wet, and which ampacity column applies to it. Here is every common type side by side, with a full page for each.

Type Dry rating Wet rating Ampacity column Installation Direct burial Typical use
THHN / THWN-290°C90°C (THWN-2)75°CRaceway requiredNoConduit branch circuits and feeders
NM-B (Romex)90°CNot permitted60°CExposed / concealed indoorsNoResidential branch circuits
XHHW / XHHW-290°C90°C (XHHW-2)75°CRaceway requiredNoFeeders, services, large aluminum
USE-290°C90°C75°CDirect burialYesUnderground services and feeders
UF-B90°CYes60°CDirect burialYesOutdoor branch circuits
SOOW / SJOOW90°CYes (W rating)Table 400.5Portable onlyNoTools, temporary power, machine drops
Welding cable105°CJacket dependentManufacturerNot NEC building wireNoWelding leads, battery and inverter runs
Speaker wiren/aBurial-rated types onlyn/aCL2 / CL3 in wallRated types onlyLoudspeaker runs, Class 2 circuits

The ampacity column is the one that catches people out. NM-B and UF-B contain 90°C conductors but are restricted to the 60°C column by NEC 334.80 and 340.80 respectively, which is why 6 AWG Romex will not carry a 60 A load while 6 AWG THHN in conduit will.

Wire Type Pages

THHN / THWN-2

THHN/THWN-2 is a 600 V building wire rated 90°C in dry and wet locations, with PVC insulation and a nylon jacket. It must be run in conduit or a …

Romex (NM-B)

Romex (NM-B) ampacity comes from the 60°C column: 14 AWG is 15 A, 12 AWG is 20 A, 10 AWG is 30 A, 6 AWG is 55 A. Full size chart with sheath colo…

XHHW / XHHW-2

XHHW-2 is a 600 V building wire with cross-linked polyethylene insulation rated 90°C wet and dry. Full ampacity table, how it differs from THHN, …

USE-2

USE-2 is a 90°C wet-rated single conductor listed for direct burial without a raceway. It has no flame rating, so it may not be run inside a buil…

UF-B

UF-B is grey direct-burial branch circuit cable rated 60°C for ampacity: 14 AWG is 15 A, 12 AWG is 20 A, 10 AWG is 30 A. Burial depth requirement…

SOOW / SJOOW

SOOW is 600 V oil-resistant, weather-resistant portable cord; SJOOW is the 300 V junior version. Ampacity from NEC Table 400.5, what every letter…

Welding Cable

Welding cable is 600 V, 105°C, extremely fine-stranded EPDM cable built for flexibility, not for building wiring. Ampacity by duty cycle, Class K…

Speaker Wire

Speaker wire is unshielded low-voltage cable in 12 to 18 AWG. Which gauge for your run length and impedance, what CL2 and CL3 in-wall ratings mea…

Reading the letter code

Wire type designations are built from a fixed set of letters. Once you know them, an unfamiliar marking parses on sight:

So THWN-2 reads as thermoplastic, heat resistant, wet rated, nylon jacketed, 90°C wet. XHHW-2 is cross-linked, high heat resistant, wet rated, 90°C wet. USE-2 is underground service entrance, 90°C wet.

Frequently Asked Questions

What is the difference between THHN and Romex?

THHN is a single insulated conductor that must be pulled through conduit. Romex (NM-B) is a complete cable assembly with two or three insulated conductors and a bare ground inside a sheath, run exposed or concealed in dry indoor locations. THHN uses the 75°C ampacity column in practice; NM-B is restricted to the 60°C column.

Which wire types can be buried directly in the ground?

USE-2 for service and feeder conductors, and UF-B for branch circuits. Both are listed for direct burial without a raceway. THHN, THWN-2, XHHW-2 and NM-B may not be direct buried — the first three require a raceway and NM-B is prohibited underground entirely.

Which ampacity column applies to which wire type?

NM-B and UF-B are restricted to the 60°C column by NEC 334.80 and 340.80. THHN, THWN-2, XHHW-2 and USE-2 use the 90°C column as the derating basis, but are limited to 75°C at the terminations by NEC 110.14(C). Flexible cords use NEC Table 400.5 instead of Table 310.16 entirely.

What do the letters in wire type names mean?

T is thermoplastic, H is heat resistant to 75°C, HH is high heat resistant to 90°C, W is wet location rated, N is a nylon jacket, X is cross-linked polyethylene, and a -2 suffix means 90°C in wet locations as well as dry. So THWN-2 is thermoplastic, high heat, wet rated, nylon jacketed, 90°C wet.

Related

Conductor materials and resistivity → NEC Table 310.16 — conductor ampacity → Conduit fill charts → Solid vs stranded conductors → Ampacity tables →