SOOW and SJOOW Portable Cord — Ampacity and Ratings

SOOW and SJOOW are flexible portable cords covered by NEC Article 400. The letters are a specification, not a brand: S for 600 V service cord, J for the 300 V junior version, OO for oil-resistant jacket and oil-resistant insulation, and W for weather and water resistance including sunlight. Ampacity comes from NEC Table 400.5(A)(1), not from Table 310.16.

SOOW / SJOOW — Specifications

PropertyValue
SOOW voltage rating600 V
SJOOW voltage rating300 V
Temperature ratingTypically −40°C to 90°C; 105°C versions exist
JacketThermoset CPE or neoprene, oil and weather resistant
ConductorFine-stranded annealed copper for flexibility
Sizes18 AWG through 2 AWG
NEC articleArticle 400, ampacity from Table 400.5(A)(1)
Sunlight resistanceYes — that is what the W denotes
Fixed wiringNot permitted as a substitute (NEC 400.12)
Typical usePortable tools, temporary power, stage and event, machine drops
Specifications reflect the common commercial product and the governing NEC article. Always confirm the markings printed on the conductor or jacket, which are the authoritative statement of what a given reel is listed for.

SOOW / SJOOW Ampacity — NEC Table 400.5(A)(1)

SizeColumn A — 2 current-carrying conductorsColumn B — 3 current-carrying conductors
18 AWG10 A7 A
16 AWG13 A10 A
14 AWG18 A15 A
12 AWG25 A20 A
10 AWG30 A25 A
8 AWG40 A35 A
6 AWG55 A45 A
4 AWG70 A60 A
2 AWG95 A80 A
Ampacity for flexible cords and cables. Where four to six current-carrying conductors are present, apply an 80% adjustment; for seven to nine, 70%. A grounding conductor is not counted as current-carrying. These values are materially lower than the building-wire figures in Table 310.16 — do not substitute one table for the other.

Reading the letter codes

S — hard service cord, 600 V. SJ — junior hard service, 300 V, thinner jacket, lighter duty. E — thermoplastic elastomer insulation. O — oil-resistant jacket. OO — oil-resistant jacket and oil-resistant conductor insulation. W — weather and water resistant, and suitable for outdoor use including sunlight exposure.

So SOOW is 600 V, oil resistant inside and out, weather rated. SJOOW is the same construction at 300 V. SOW would be oil-resistant jacket only. The order of the letters is fixed by the standard, which is why the codes look cryptic but parse cleanly once you know the key.

Cord is not fixed wiring

NEC 400.12 is explicit about what flexible cord may not do, and it is the most violated rule in Article 400. Cord may not be used as a substitute for the fixed wiring of a structure. It may not be run through holes in walls, ceilings or floors, or through doorways and windows. It may not be concealed behind walls or above suspended ceilings, or attached to building surfaces except where specifically permitted.

The permitted uses in NEC 400.10 are the mirror image: pendants, wiring of luminaires, connection of portable equipment, elevator cables, connection of appliances designed for ready removal, and equipment that must be moved for maintenance. If the load is not intended to move or be removed, it needs building wire in a raceway or a cable assembly, not cord.

Ampacity comes from a different table

Because cord conductors are fine-stranded and bundled in a flexible jacket with no air gap, they use NEC Table 400.5(A)(1) rather than Table 310.16. Column A applies to cords with two current-carrying conductors, Column B to cords with three. Cords with four to six current-carrying conductors derate to 80%, and seven to nine to 70%.

The values are meaningfully lower than building wire. 12 AWG SOOW with three conductors is 20 A, matching 12 AWG THHN by coincidence — but 6 AWG SOOW is 45 A where 6 AWG THHN in conduit is 65 A. Size portable cord from Table 400.5, never from the building wire tables.

Other Wire Types