Wire Ampacity Tables

Allowable ampacities of insulated conductors based on NEC Table 310.16. Not more than 3 current-carrying conductors in raceway or cable, 30°C ambient temperature.

Copper Ampacity at 75°C by Gauge

Copper Wire Ampacity Bar Chart at 75°C Horizontal bar chart showing copper ampacity at 75°C for gauges 14 AWG through 4/0 AWG, color-coded by use category: blue for light-duty, amber for general, red for heavy-duty. Light-duty (15-20A) General (25-65A) Heavy-duty (85A+) 14 AWG 20A 12 AWG 25A 10 AWG 35A 8 AWG 50A 6 AWG 65A 4 AWG 85A 3 AWG 100A 2 AWG 115A 1 AWG 130A 1/0 150A 2/0 175A 4/0 230A Ampacity values from NEC Table 310.16 — Copper, 75°C (THWN/THWN-2)
AWG Cu 60°C
(TW, UF)
Cu 75°C
(THWN)
Cu 90°C
(THHN)
Al 75°C
4/0 195 230 260 180
3/0 165 200 225 155
2/0 145 175 195 135
1/0 125 150 170 120
1 110 130 145 100
2 95 115 130 90
3 85 100 115 75
4 70 85 95 65
6 55 65 75 50
8 40 50 55 40
10 30 35* 40 30
12 20 25* 30 20
14 15 20* 25 —
16 — — 18† —
18 — — 14† —

Note: These ampacity values assume no more than 3 current-carrying conductors in a raceway, cable, or direct burial at 30°C ambient temperature. Derate for higher temperatures, more conductors, or conduit fill per NEC 310.15.
* NEC 240.4(D) caps overcurrent protection at 15A (14 AWG), 20A (12 AWG) and 30A (10 AWG) copper; 15A and 25A for 12 and 10 AWG aluminum. † 18 and 16 AWG appear only in the 90°C column and are not permitted for general branch circuits.

Frequently Asked Questions

What is ampacity?

Ampacity is the maximum continuous current (in amps) a wire can carry safely without overheating its insulation. NEC Table 310.16 lists ampacity for conductors in conduit at ambient temperature of 30°C (86°F).

What is the ampacity of 12 AWG copper wire?

12 AWG copper wire has an ampacity of 20A at 60°C, 25A at 75°C, and 30A at 90°C insulation rating per NEC Table 310.16. NEC 240.4(D) still limits it to a 20A breaker, and NM-B cable must use the 60°C column (NEC 334.80).

Why does insulation temperature affect ampacity?

Higher-rated insulation can withstand more heat, allowing more current through the same conductor. NEC publishes ampacity values at 60°C, 75°C, and 90°C. THHN/THWN-2 is rated 90°C wet or dry, but the usable ampacity is limited by the lowest-rated termination (NEC 110.14(C)): usually 75°C for THHN in conduit, and 60°C for NM-B cable or equipment 100A and below not marked 75°C.

What is the ampacity of 10 AWG wire?

10 AWG copper wire has an ampacity of 30A at 60°C, 35A at 75°C, and 40A at 90°C per NEC Table 310.16. 10 AWG aluminum wire rates at 25A (60°C), 30A (75°C), 35A (90°C).

Related

Circuit breaker size chart → Wire types and insulation ratings → NEC Table 310.16 — conductor ampacity → NEC Table 310.15 — derating factors →