Wire Ampacity Tables

Allowable ampacities of insulated conductors based on NEC Table 310.16. Not more than 3 current-carrying conductors in raceway or cable, 30°C ambient temperature.

AWG Cu 60°C
(TW, UF)
Cu 75°C
(THWN)
Cu 90°C
(THHN)
Al 75°C
4/0 195 230 260 180
3/0 165 200 225 155
2/0 145 175 195 135
1/0 125 150 170 120
1 110 130 145 100
2 95 115 130 90
3 85 100 115 75
4 70 85 95 65
6 55 65 75 50
8 40 50 55 40
10 30 35 40 30
12 20 25 30 20
14 15 20 25 None
16 None 13 18 None
18 None 10 14 None

Note: These ampacity values assume no more than 3 current-carrying conductors in a raceway, cable, or direct burial at 30°C ambient temperature. Derate for higher temperatures, more conductors, or conduit fill per NEC 310.15.