2 AWG Wire

2 AWG (American Wire Gauge) wire specifications: 6.5437 mm diameter, 33.6308 mm² area, 115A ampacity (copper, 75°C). Resistance, weight, and common uses.

Diameter
6.5437 mm
0.257626"
Area
33.6308 mm²
66,371 cmil
Ampacity (Cu)
115A
75°C insulation
Resistance (Cu)
0.5126
Ω/km at 20°C

2 AWG — Complete Specifications

Diameter6.5437 mm · 0.257626" · 257.63 mils
Cross-sectional area33.6308 mm² · 66,371 circular mils
Resistance (copper, 20°C)0.5126 Ω/km · 0.1562 Ω/1000ft
Resistance (aluminum, 20°C)0.8403 Ω/km · 0.2561 Ω/1000ft
Ampacity — copper 60°C95 A
Ampacity — copper 75°C115 A
Ampacity — copper 90°C130 A
Ampacity — aluminum 75°C90 A
Weight (copper)301.332 kg/km · 202.486 lbs/1000ft
Weight (aluminum)90.803 kg/km · 61.017 lbs/1000ft
Closest IEC 60228 size35 mm²
Skin depth at 60 Hz8.531 mm

Common Uses for 2 AWG Wire

Compatible Insulation Types

TypeTemperatureDescription
THHN/THWN-2 90°C dry / 75°C wet Most common for building wire
XHHW-2 90°C dry and wet Cross-linked polyethylene, moisture resistant
USE-2 90°C Underground service entrance
NM-B (Romex) 90°C Non-metallic sheathed cable for residential
UF-B 60°C Underground feeder, direct burial

Frequently Asked Questions

What is 2 AWG wire used for?

2 AWG copper is commonly used for large feeders and subpanels around 90–100A. NEC Table 310.16 rates it 115A at 75°C. It measures 6.544 mm in diameter with a 33.6 mm² cross-section.

What is the ampacity of 2 AWG wire?

Per NEC Table 310.16 (30°C ambient, no more than three current-carrying conductors), 2 AWG copper is rated 95A at 60°C, 115A at 75°C and 130A at 90°C. 2 AWG aluminum is rated 75A, 90A and 100A in the same columns. On circuits of 100A or less, NEC 110.14(C) generally requires the 60°C column unless every termination is rated 75°C.

Is 2 AWG wire available in aluminum?

Yes. 2 AWG aluminum is rated 90A at 75°C versus 115A for copper, so matching the copper rating takes 1/0 AWG aluminum. Aluminum at this size is common for feeders, subpanels and service conductors (SER, USE-2, XHHW-2). Use AL-rated lugs, torque to the manufacturer’s spec and apply antioxidant compound where required.

2 AWG voltage drop by distance

Explore

Conduit fill charts → Wire types and insulation ratings → Full AWG chart → Wire size calculator → AWG to mm² converter → Ampacity tables → Wire materials →