Wire gauge reference & calculator

AWG to mm² Conversion

Convert American Wire Gauge (AWG) sizes to metric cross-sectional area in square millimeters (mm²). The AWG system is used in North America; most of the world uses mm² (IEC 60228).

AWG mm² Diameter (mm) Diameter (in) Circular Mils
4/0 107.2193 11.684 0.46 211,600
3/0 85.0288 10.4049 0.409642 167,806
2/0 67.4309 9.2658 0.364797 133,076
1/0 53.4751 8.2515 0.324861 105,534
1 42.4077 7.3481 0.289297 83,693
2 33.6308 6.5437 0.257626 66,371
3 26.6705 5.8273 0.229423 52,635
4 21.1506 5.1894 0.204307 41,741
5 16.7732 4.6213 0.181941 33,102
6 13.3018 4.1154 0.162023 26,251
7 10.5488 3.6649 0.144285 20,818
8 8.3656 3.2636 0.12849 16,510
9 6.6342 2.9064 0.114424 13,093
10 5.2612 2.5882 0.101897 10,383
11 4.1723 2.3048 0.090742 8,234
12 3.3088 2.0525 0.080808 6,530
13 2.624 1.8278 0.071962 5,178
14 2.0809 1.6277 0.064084 4,107
15 1.6502 1.4495 0.057068 3,257
16 1.3087 1.2908 0.050821 2,583
17 1.0378 1.1495 0.045257 2,048
18 0.823 1.0237 0.040303 1,624
19 0.6527 0.9116 0.035891 1,288
20 0.5176 0.8118 0.031961 1,022
21 0.4105 0.7229 0.028462 810
22 0.3255 0.6438 0.025347 642
23 0.2582 0.5733 0.022572 510
24 0.2047 0.5106 0.020101 404
25 0.1624 0.4547 0.0179 320
26 0.1288 0.4049 0.015941 254
27 0.1021 0.3606 0.014196 202
28 0.081 0.3211 0.012641 160
29 0.0642 0.2859 0.011258 127
30 0.0509 0.2546 0.010025 100
31 0.0404 0.2268 0.008928 80
32 0.032 0.2019 0.00795 63
33 0.0254 0.1798 0.00708 50
34 0.0201 0.1601 0.006305 40
35 0.016 0.1426 0.005615 32
36 0.0127 0.127 0.005 25

AWG to mm² Formula

The cross-sectional area in mm² for any AWG gauge can be calculated:

Area (mm²) = (π/4) × [0.127 × 92(36-n)/39]²

Note that AWG and IEC metric sizes don't have exact 1:1 equivalents. A 12 AWG wire (3.31 mm²) is closest to the 4 mm² IEC standard size, but they are not identical.

Frequently Asked Questions

How do I convert AWG to mm²?

The formula is: diameter (mm) = 0.127 × 92^((36-AWG)/39), then area (mm²) = π/4 × diameter². For example, 12 AWG has a diameter of 2.053 mm and an area of 3.31 mm². Use the table on this page for quick lookup without calculation.

Is 4 mm² the same as 12 AWG?

4 mm² (IEC standard size) is not exactly 12 AWG. 12 AWG has an area of 3.31 mm², while 4 mm² is slightly larger (closer to 11 AWG). When substituting, 4 mm² is a safe and conservative replacement for 12 AWG wire in metric-standard wiring.

What AWG is 6 mm²?

6 mm² is closest to 9 AWG (not a standard US size). The nearest standard AWG sizes are 10 AWG (5.26 mm², slightly smaller) or 8 AWG (8.37 mm², larger). When converting, 6 mm² and 10 AWG are often used interchangeably in practical applications.