What wire size does each breaker need, what ground wire goes with it, and how much load it can actually carry. Conductor sizes follow the 75°C column of NEC Table 310.16; grounds follow NEC Table 250.122.
| Breaker | Copper | Aluminum | Ground (Cu) | Max continuous | Poles | Typical use |
|---|---|---|---|---|---|---|
| 15A | 14 AWG | 12 AWG | 14 AWG | 12 A | Single-pole | General lighting circuits |
| 20A | 12 AWG | 10 AWG | 12 AWG | 16 A | Single-pole | Kitchen small-appliance circuits |
| 30A | 10 AWG | 8 AWG | 10 AWG | 24 A | Double-pole | Electric clothes dryers |
| 40A | 8 AWG | 6 AWG | 10 AWG | 32 A | Double-pole | Electric ranges and cooktops |
| 50A | 6 AWG | 4 AWG | 10 AWG | 40 A | Double-pole | Electric ranges |
| 60A | 6 AWG | 4 AWG | 10 AWG | 48 A | Double-pole | Sub-panels |
| 100A | 1 AWG | 1/0 AWG | 8 AWG | 80 A | Double-pole | Main service for a small home |
| 200A | 4/0 AWG | 4/0 AWG | 6 AWG | 160 A | Double-pole | Standard main service for a modern single-family home |
Maximum continuous load is 80% of the breaker rating, the inverse of the 125% sizing requirement in NEC 210.20(A). Non-continuous loads may use the full breaker rating.
This is the single idea behind every number on this page. A circuit breaker exists to open the circuit before the conductor overheats. It is chosen to match the wire, not the appliance. An appliance that trips a correctly sized breaker is drawing more than the circuit was built for — the answer is a bigger circuit, never a bigger breaker on the same wire.
Three code rules set the ceiling, and the smallest one wins. Table 310.16 gives the conductor ampacity. NEC 240.4(D) caps 14, 12 and 10 AWG copper at 15, 20 and 30 A regardless of what the table says. NEC 110.14(C) limits you to the termination temperature rating, normally 75°C, even when the conductor is 90°C THHN.
Then two more can pull the required conductor larger: 310.15 derating for hot ambients or crowded raceways, and voltage drop on long runs.