WireSizing
Wire gauge reference & calculator

40 Amp Breaker Wire Size

Copper Wire
8 AWG
Aluminum Wire
6 AWG
Ground (Copper)
10 AWG
Double-pole · 240 V · Max continuous load 32 A · NEC Tables 310.16 and 250.122

40 Amp Circuit — Specification Summary

ItemValue
Breaker typeDouble-pole, 240 V
Recommended copper conductor8 AWG
Recommended aluminum conductor6 AWG
Minimum per NEC Table 310.16, 75°C8 AWG copper (50 A)
Minimum NM-B cable, 60°C column8 AWG copper (40 A)
Equipment grounding conductor10 AWG copper / 8 AWG aluminum (NEC Table 250.122)
Maximum continuous load (125% rule)32 A
Maximum non-continuous load40 A
Recommended conductor sizes follow the 75°C column of NEC Table 310.16, the column that matches the termination rating of virtually all modern breakers and lugs (NEC 110.14(C)).

Common Uses for 40 A Circuits

Electric ranges and cooktops, 32 A Level 2 EV chargers, larger central air conditioning, electric furnaces

What a 40 Amp Breaker Powers

LoadNotes
Electric range / cooktop40 A is common for cooktops and smaller ranges
Level 2 EV charger (32 A)32 × 1.25 = 40 A circuit — NEC 625.41
Central air conditionerSize from the nameplate MCA and MOCP
Electric furnace / air handlerOften multiple circuits
Always size a circuit from the equipment nameplate or a load calculation, not from a general table. Air conditioners and heat pumps in particular carry a minimum circuit ampacity (MCA) and maximum overcurrent protective device (MOCP) rating that override the general rules.

NEC requirements for this circuit

40 A is where the 125% continuous-load rule starts to bite. An EV charger or an electric heater runs for more than three hours, so the circuit must be rated at 125% of the load: a 32 A charger needs a 40 A circuit, not a 32 A one.

Outdoor and garage receptacle outlets up to 250 V require GFCI protection under NEC 210.8(A). Hard-wired appliances are generally exempt unless a specific article requires it.

Voltage Drop by Distance — 8 AWG Copper at 40 A

One-way runDrop% of 240VVerdict
25 ft1.56 V0.6%Within the 3% branch-circuit target
50 ft3.11 V1.3%Within the 3% branch-circuit target
75 ft4.67 V1.9%Within the 3% branch-circuit target
100 ft6.22 V2.6%Within the 3% branch-circuit target
150 ft9.34 V3.9%Over 3% — upsize one gauge
200 ft12.45 V5.2%Well over 3% — upsize two gauges or more
Single-phase, 240V, full 40 A load, 0.778 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. See the voltage drop formula for the arithmetic.

The 80% rule: a continuous load is one expected to run for three hours or more — EV chargers, electric heat, and most commercial lighting. NEC 210.20(A) requires the overcurrent device to be rated at not less than 125% of that continuous load, which leaves 32 A usable on a 40 A breaker. A breaker that trips after an hour or two under a steady load is usually a continuous-load sizing mistake, not a faulty breaker.

Other Breaker Sizes

Related

Wire size for 40 amps — full page → 8 AWG full specifications → NEC Table 250.122 — ground wire size → NEC Table 310.16 — conductor ampacity → Wire size calculator →