Electric ranges, large AC units
| Diameter | 3.2636 mm (0.12849") |
| Area | 8.3656 mm² |
| Resistance at 20°C | 2.0608 Ω/km |
| Weight | 74.955 kg/km |
| Ampacity (75°C) | 50 A |
Important: For long wire runs, you may need to upsize the wire to compensate for voltage drop. NEC recommends keeping voltage drop under 3% for branch circuits. Use our voltage drop calculator to check.
| One-way run | Drop | % of 240V | Verdict |
|---|---|---|---|
| 25 ft | 1.26 V | 0.5% | Within the 3% branch-circuit target |
| 50 ft | 2.51 V | 1.0% | Within the 3% branch-circuit target |
| 75 ft | 3.77 V | 1.6% | Within the 3% branch-circuit target |
| 100 ft | 5.02 V | 2.1% | Within the 3% branch-circuit target |
| 150 ft | 7.54 V | 3.1% | Over 3% — upsize one gauge |
| 200 ft | 10.05 V | 4.2% | Over 3% — upsize one gauge |