What Wire Size for 40 Amps?

Copper Wire
8 AWG
3.2636 mm · 8.3656 mm²
Aluminum Wire
6 AWG
4.1154 mm · 13.3018 mm²
Breaker: 40A · Based on NEC Table 310.16, 60°C column (the NEC 110.14(C) default at 100A or less)

40-Amp Wire Size by Termination Rating

RuleCopperAluminum
60°C column — NM-B cable, or any termination not marked 75°C8 AWG6 AWG
75°C column — THHN/THWN-2 with 75°C-rated breaker and lugs8 AWG8 AWG

Most breakers and panelboards rated 100A or less are listed 60/75°C, but NM-B cable is always limited to the 60°C column (NEC 334.80). When in doubt, use the 60°C answer.

Common Uses for 40A Circuits

Electric ranges, large AC units

8 AWG Copper — Key Specs

Diameter3.2636 mm (0.12849")
Area8.3656 mm²
Resistance at 20°C2.0608 Ω/km
Weight74.955 kg/km
Ampacity (75°C)50 A

Important: For long wire runs, you may need to upsize the wire to compensate for voltage drop. NEC recommends keeping voltage drop under 3% for branch circuits. Use our voltage drop calculator to check.

Voltage Drop by Distance — 8 AWG Copper at 40A

One-way run Drop % of 240V Verdict
25 ft1.56 V0.6%Within the 3% branch-circuit target
50 ft3.11 V1.3%Within the 3% branch-circuit target
75 ft4.67 V1.9%Within the 3% branch-circuit target
100 ft6.22 V2.6%Within the 3% branch-circuit target
150 ft9.34 V3.9%Over 3% — upsize one gauge
200 ft12.45 V5.2%Over 5% — upsize at least two gauges
Single-phase, 240V, full 40A load, 0.778 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. Voltage drop is a performance recommendation, not a code requirement — but exceeding it causes dim lights, slow motor starts, and wasted energy.

Related Appliance Guides

Frequently Asked Questions

What wire size do I need for 40 amps?

Using the 60°C column of NEC Table 310.16, which NEC 110.14(C) requires by default for circuits of 100A or less and always for NM-B cable, a 40-amp circuit needs 8 AWG copper or 6 AWG aluminum. With THHN/THWN-2 conductors and breakers and lugs rated 75°C, 8 AWG copper or 8 AWG aluminum is permitted.

What breaker do I need for 40 amps?

A 40-amp circuit uses a 40A double-pole circuit breaker. The breaker protects the 8 AWG copper (or 6 AWG aluminum) wire from overload. Double-pole breakers are used for 240V circuits and occupy two slots in the panel.

What wire size for an electric stove on a 40-amp circuit?

A 40-amp electric range circuit uses 8 AWG copper or 6 AWG aluminum wire on a 40A double-pole breaker. Note: most modern full-size electric ranges are now rated for 50A circuits instead.

Can a 40-amp breaker use 10 AWG wire?

No — 10 AWG copper wire is rated for 30A maximum. For a 40-amp circuit you must use at least 8 AWG copper or 6 AWG aluminum wire. Using undersized wire on an oversized breaker is a serious fire hazard.

Wire size for other amperages

Related

Wire types and insulation ratings → 40 amp breaker — wire, ground and load → NEC Table 250.122 — ground wire size → 8 AWG full specifications → Full AWG chart → Wire size calculator → Ampacity tables →