What Wire Size for 100 Amps?

Copper Wire
1 AWG
7.3481 mm · 42.4077 mm²
Aluminum Wire
1/0 AWG
8.2515 mm · 53.4751 mm²
Breaker: 100A · Based on NEC Table 310.16, 60°C column (the NEC 110.14(C) default at 100A or less)

100-Amp Wire Size by Termination Rating

RuleCopperAluminum
60°C column — NM-B cable, or any termination not marked 75°C1 AWG1/0 AWG
75°C column — THHN/THWN-2 with 75°C-rated breaker and lugs3 AWG1 AWG
Dwelling service or main feeder — NEC 310.12 (83% = 83A)4 AWG2 AWG

Most breakers and panelboards rated 100A or less are listed 60/75°C, but NM-B cable is always limited to the 60°C column (NEC 334.80). When in doubt, use the 60°C answer.

Common Uses for 100A Circuits

Main panels, large sub-panels, service entrance

1 AWG Copper — Key Specs

Diameter7.3481 mm (0.289297")
Area42.4077 mm²
Resistance at 20°C0.4065 Ω/km
Weight379.973 kg/km
Ampacity (75°C)130 A

Important: For long wire runs, you may need to upsize the wire to compensate for voltage drop. NEC recommends keeping voltage drop under 3% for branch circuits. Use our voltage drop calculator to check.

Voltage Drop by Distance — 1 AWG Copper at 100A

One-way run Drop % of 240V Verdict
25 ft0.77 V0.3%Within the 3% branch-circuit target
50 ft1.54 V0.6%Within the 3% branch-circuit target
75 ft2.31 V1.0%Within the 3% branch-circuit target
100 ft3.08 V1.3%Within the 3% branch-circuit target
150 ft4.62 V1.9%Within the 3% branch-circuit target
200 ft6.16 V2.6%Within the 3% branch-circuit target
Single-phase, 240V, full 100A load, 0.154 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. Voltage drop is a performance recommendation, not a code requirement — but exceeding it causes dim lights, slow motor starts, and wasted energy.

Aluminum Feeder Specifications

Aluminum has about 61% of copper’s conductivity, so a 100A feeder that takes 1 AWG copper needs 1/0 AWG aluminum — typically one to two gauge sizes larger.

Aluminum conductor1/0 AWG
Ampacity (75°C, Table 310.16)120 A
Copper equivalent1 AWG (130 A)
Resistance0.151 Ω/1000 ft
Voltage drop at 100 ft, 100A4.02 V (1.7% of 240V)

Installing aluminum correctly

  • Modern aluminum building wire must be AA-8000 series alloy (NEC 310.14(A)(1)). The 1960s-era AA-1350 alloy behind aluminum’s bad reputation is no longer permitted for branch circuits.
  • Terminate only on lugs and breakers marked AL/CU or AL9CU. Copper-only terminals are the most common failure point.
  • Apply an antioxidant compound to the stripped conductor before landing it, unless the termination is listed as not requiring it.
  • Torque every connection to the manufacturer’s value with a calibrated torque tool — NEC 110.14(D) makes this mandatory. Loose aluminum terminations are the primary cause of feeder failures.
  • Aluminum runs roughly half the weight and a third to half the cost of copper at feeder sizes, which is why it dominates service entrance and sub-panel feeders.

Frequently Asked Questions

What wire size do I need for 100 amps?

Using the 60°C column of NEC Table 310.16, which NEC 110.14(C) requires by default for circuits of 100A or less and always for NM-B cable, a 100-amp circuit needs 1 AWG copper or 1/0 AWG aluminum. With THHN/THWN-2 conductors and breakers and lugs rated 75°C, 3 AWG copper or 1 AWG aluminum is permitted.

What breaker do I need for 100 amps?

A 100-amp circuit uses a 100A double-pole circuit breaker. The breaker protects the 1 AWG copper (or 1/0 AWG aluminum) wire from overload. Double-pole breakers are used for 240V circuits and occupy two slots in the panel.

What wire size for a 100-amp service entrance?

A 100-amp dwelling service can be sized under NEC 310.12 at 83% of the rating (83A): 4 AWG copper or 2 AWG aluminum, the familiar #4 Cu / #2 Al service. A 100A feeder to a sub-panel does not get that allowance and needs 1 AWG copper or 1/0 aluminum at 60°C, or 3 AWG copper or 1 AWG aluminum with 75°C terminations.

What does a 100-amp panel support?

A 100-amp panel (with correctly sized service conductors) can power a small to medium home. It supports a mix of 15A and 20A branch circuits, plus one or two 240V appliances like a range or dryer — but may be limiting for homes with EV chargers or electric heat.

Wire size for other amperages

Related

Wire types and insulation ratings → 100 amp breaker — wire, ground and load → NEC Table 250.122 — ground wire size → 1 AWG full specifications → Full AWG chart → Wire size calculator → Ampacity tables →