What Wire Size for 30 Amps?

Copper Wire
10 AWG
2.5882 mm · 5.2612 mm²
Aluminum Wire
8 AWG
3.2636 mm · 8.3656 mm²
Breaker: 30A · Based on NEC Table 310.16 (75°C insulation)

Common Uses for 30A Circuits

Dryers, water heaters, small AC units

10 AWG Copper — Key Specs

Diameter2.5882 mm (0.101897")
Area5.2612 mm²
Resistance at 20°C3.2768 Ω/km
Weight47.14 kg/km
Ampacity (75°C)35 A

Important: For long wire runs, you may need to upsize the wire to compensate for voltage drop. NEC recommends keeping voltage drop under 3% for branch circuits. Use our voltage drop calculator to check.

NEC 240.4(D) — why 10 AWG and not something smaller

NEC Table 310.16 rates 10 AWG copper at 35 A at 75°C, which looks like more headroom than a 30A circuit needs. It is not usable headroom. NEC 240.4(D), the small-conductor rule, caps the overcurrent device on 10 AWG copper at 30 A regardless of what the ampacity table says.

This is why 10 AWG is the answer for a 30A circuit and why the next size down is not: the smaller conductor’s own 240.4(D) cap falls below 30 A. Any calculator that reads Table 310.16 without applying 240.4(D) will hand you an undersized, code-violating conductor.

The rule covers 18 through 10 AWG copper and 12 through 10 AWG aluminum. NEC 240.4(E) and 240.4(G) carve out narrow exceptions — tap conductors, motor circuits, air-conditioning equipment, and welders are sized under their own articles instead. See the full table on the wire size calculator.

Voltage Drop by Distance — 10 AWG Copper at 30A

One-way run Drop % of 240V Verdict
25 ft1.50 V0.6%Within the 3% branch-circuit target
50 ft3.00 V1.2%Within the 3% branch-circuit target
75 ft4.49 V1.9%Within the 3% branch-circuit target
100 ft5.99 V2.5%Within the 3% branch-circuit target
150 ft8.99 V3.7%Over 3% — upsize one gauge
200 ft11.99 V5.0%Over 3% — upsize one gauge
Single-phase, 240V, full 30A load, 0.9988 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. Voltage drop is a performance recommendation, not a code requirement — but exceeding it causes dim lights, slow motor starts, and wasted energy.