What Wire Size for 30 Amps?

Copper Wire
10 AWG
2.5882 mm · 5.2612 mm²
Aluminum Wire
8 AWG
3.2636 mm · 8.3656 mm²
Breaker: 30A · Based on NEC Table 310.16, 60°C column (the NEC 110.14(C) default at 100A or less)

30-Amp Wire Size by Termination Rating

RuleCopperAluminum
60°C column — NM-B cable, or any termination not marked 75°C10 AWG8 AWG
75°C column — THHN/THWN-2 with 75°C-rated breaker and lugs10 AWG8 AWG

Most breakers and panelboards rated 100A or less are listed 60/75°C, but NM-B cable is always limited to the 60°C column (NEC 334.80). When in doubt, use the 60°C answer.

Common Uses for 30A Circuits

Dryers, water heaters, small AC units

10 AWG Copper — Key Specs

Diameter2.5882 mm (0.101897")
Area5.2612 mm²
Resistance at 20°C3.2768 Ω/km
Weight47.14 kg/km
Ampacity (75°C)35 A

Important: For long wire runs, you may need to upsize the wire to compensate for voltage drop. NEC recommends keeping voltage drop under 3% for branch circuits. Use our voltage drop calculator to check.

NEC 240.4(D) — why 10 AWG and not something smaller

NEC Table 310.16 rates 10 AWG copper at 35 A at 75°C, which looks like more headroom than a 30A circuit needs. It is not usable headroom. NEC 240.4(D), the small-conductor rule, caps the overcurrent device on 10 AWG copper at 30 A regardless of what the ampacity table says.

This is why 10 AWG is the answer for a 30A circuit and why the next size down is not: the smaller conductor’s own 240.4(D) cap falls below 30 A. Any calculator that reads Table 310.16 without applying 240.4(D) will hand you an undersized, code-violating conductor.

The rule covers 18 through 10 AWG copper and 12 through 10 AWG aluminum. NEC 240.4(E) and 240.4(G) carve out narrow exceptions — tap conductors, motor circuits, air-conditioning equipment, and welders are sized under their own articles instead. See the full table on the wire size calculator.

Voltage Drop by Distance — 10 AWG Copper at 30A

One-way run Drop % of 240V Verdict
25 ft1.86 V0.8%Within the 3% branch-circuit target
50 ft3.72 V1.6%Within the 3% branch-circuit target
75 ft5.58 V2.3%Within the 3% branch-circuit target
100 ft7.44 V3.1%Over 3% — upsize one gauge
150 ft11.16 V4.7%Over 3% — upsize one gauge
200 ft14.88 V6.2%Over 5% — upsize at least two gauges
Single-phase, 240V, full 30A load, 1.24 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. Voltage drop is a performance recommendation, not a code requirement — but exceeding it causes dim lights, slow motor starts, and wasted energy.

Related Appliance Guides

Frequently Asked Questions

What wire size do I need for 30 amps?

Using the 60°C column of NEC Table 310.16, which NEC 110.14(C) requires by default for circuits of 100A or less and always for NM-B cable, a 30-amp circuit needs 10 AWG copper or 8 AWG aluminum. NEC 240.4(D) sets the minimum here: 10 AWG copper may not be protected above 30A.

What breaker do I need for 30 amps?

A 30-amp circuit uses a 30A double-pole circuit breaker. The breaker protects the 10 AWG copper (or 8 AWG aluminum) wire from overload. Double-pole breakers are used for 240V circuits and occupy two slots in the panel.

What appliances need a 30-amp circuit?

Common 30-amp, 240V appliances include electric dryers, electric water heaters, window or wall air conditioners (up to 240V), and some smaller electric ranges. All require 10 AWG copper or 8 AWG aluminum wire.

Can I use 12 AWG for a 30-amp dryer circuit?

No — 12 AWG is only rated for 20A and would be a code violation and fire hazard on a 30A breaker. Electric dryers require 10 AWG copper (or 8 AWG aluminum) wire and a 30-amp, 240V double-pole breaker.

Wire size for other amperages

Related

Wire types and insulation ratings → 30 amp breaker — wire, ground and load → NEC Table 250.122 — ground wire size → 10 AWG full specifications → Full AWG chart → Wire size calculator → Ampacity tables →