Electric Water Heater — Wire Size & Circuit Requirements

Standard 4500W electric water heaters draw about 18.75 amps at 240V and require a dedicated 30-amp circuit.

Wire Size
10 AWG
Breaker
30A double-pole
Voltage
240V
Typical Draw
18.75A

Wiring Specifications

Recommended wire10/2 NM-B or 10 AWG THHN
Breaker30A double-pole
Voltage240V
Typical amperage18.75A
Circuit amperage30A
NEC referenceNEC 422.13
Max recommended distanceAbout 155 feet one-way for 3% drop at 18.75A

Important Notes

Water heaters are considered continuous loads, so the circuit must be rated at 125% of the actual load. 18.75A × 1.25 = 23.4A, fitting within a 30A breaker.

Frequently Asked Questions

What wire size for an electric water heater?

10 AWG copper wire on a 30A, 240V double-pole breaker. A standard 4500W electric water heater draws approximately 18.75 amps at 240V. A dedicated circuit is required — no other loads may share it.

Does a water heater need a disconnect switch?

NEC 422.31 requires a means of disconnecting the water heater within sight of the appliance or lockable in the open position. Many water heaters include a built-in switch; otherwise, a disconnect is installed at the panel or near the unit.

Can I use 12 AWG wire for a water heater?

No — electric water heaters require a 30A circuit with 10 AWG copper wire. Using 12 AWG wire (rated for 20A) on a 30A breaker is a code violation and fire risk. Always size wire to match the breaker.

What is the difference between a 4500W and 5500W water heater?

A 4500W water heater draws 18.75A and fits on a standard 30A, 10 AWG circuit. A 5500W unit draws 22.9A and still fits within a 30A circuit's continuous load limit (30A × 80% = 24A). Both use 10 AWG copper wire and a 30A double-pole breaker.