WireSizing
Wire gauge reference & calculator

NEC Table 250.122 — Equipment Grounding Conductor

NEC Table 250.122 sizes the equipment grounding conductor from the rating of the overcurrent device ahead of the circuit — not from the circuit conductors. The four sizes that cover most residential work: 15 A → 14 AWG, 20 A → 12 AWG, up to 60 A → 10 AWG, up to 100 A → 8 AWG, all copper.

Table 250.122 — Minimum Equipment Grounding Conductor

Overcurrent device rating (A), not exceedingCopperAluminum
1514 AWG12 AWG
2012 AWG10 AWG
6010 AWG8 AWG
1008 AWG6 AWG
2006 AWG4 AWG
3004 AWG2 AWG
4003 AWG1 AWG
5002 AWG1/0 AWG
6001 AWG2/0 AWG
8001/0 AWG3/0 AWG
10002/0 AWG4/0 AWG
12003/0 AWG250 kcmil
16004/0 AWG350 kcmil
2000250 kcmil400 kcmil
2500350 kcmil600 kcmil
3000400 kcmil600 kcmil
4000500 kcmil750 kcmil
5000700 kcmil1200 kcmil
6000800 kcmil1200 kcmil
Use the first row whose rating equals or exceeds your breaker. A 30 A, 40 A, or 50 A circuit all fall under the 60 A row and take a 10 AWG copper equipment grounding conductor. Aluminum equipment grounding conductors may not be used within 18 inches of earth or in direct contact with masonry (NEC 250.120(B)).

The three rules that modify the table

250.122(A) — never smaller than the table, never larger than the circuit conductors. The equipment grounding conductor is not required to be larger than the ungrounded conductors it runs with. On a 60 A circuit wired with 6 AWG, the table already gives 10 AWG, so no conflict — but on tap conductors the rule matters.

250.122(B) — upsize the ground when you upsize the conductors. If the circuit conductors are increased in size for any reason — voltage drop being the common one — the equipment grounding conductor must be increased proportionally by circular mil area. Upsize a 20 A circuit from 12 AWG (6530 cmil) to 10 AWG (10380 cmil), a factor of 1.59, and the 12 AWG ground must grow by the same factor to at least 10380 cmil — 10 AWG.

250.122(F) — parallel runs. Where circuit conductors are run in parallel in multiple raceways, a full-size equipment grounding conductor sized from the overcurrent device must be run in each raceway. You do not divide it between them.

Why the table jumps from 20 A to 60 A

There is no 30 A, 40 A, or 50 A row in Table 250.122. The rows are maximum ratings — you round up to the next listed value. A 30 A dryer circuit, a 40 A range circuit, and a 50 A EV charger circuit all use the 60 A row and take a 10 AWG copper equipment grounding conductor.

This is why 10-3 NM-B cable ships with a 10 AWG bare ground, and why 6-3 NM-B for a 50 A circuit ships with a 10 AWG ground rather than a 6 AWG one. The ground only has to carry fault current long enough to open the breaker, not the continuous load.

Equipment grounding conductor versus grounding electrode conductor

The equipment grounding conductor (this table) is the fault-current path. It bonds metal enclosures and equipment back to the source so that a hot-to-case fault becomes a short circuit that trips the breaker. It is sized from the breaker because the breaker determines how much fault current has to flow before the circuit opens.

The grounding electrode conductor (Table 250.66) connects the system to earth. It stabilises voltage and handles lightning and line surges. It is sized from the service conductors. Earth is not a fault-current path and never has been.

Related

NEC Table 250.66 — grounding electrode conductor →Circuit breaker size charts →NEC Table 310.16 — conductor ampacity →Wire size by amps →Wire size calculator →