Metric Wire Sizes (IEC 60228)

Standard metric wire sizes used internationally. Defined by IEC 60228, these sizes are specified in mm² (square millimeters) cross-sectional area. Used in Europe, Asia, Australia, and most countries outside North America.

Size (mm²) Diameter (mm) ≈ AWG Amps (Cu) Amps (Al) Max Ω/km (Cu) kg/km (Cu)
0.5 mm² 0.798 20 3 — 36 4.48
0.75 mm² 0.977 18 6 — 24.5 6.72
1.0 mm² 1.128 17 10 — 18.1 8.96
1.5 mm² 1.382 15 14.5 — 12.1 13.44
2.5 mm² 1.784 13 19.5 16 7.41 22.4
4 mm² 2.257 11 26 21 4.61 35.84
6 mm² 2.764 9 34 27 3.08 53.76
10 mm² 3.568 7 46 36 1.83 89.6
16 mm² 4.514 5 61 49 1.15 143.36
25 mm² 5.642 3 80 63 0.727 224.0
35 mm² 6.676 2 99 77 0.524 313.6
50 mm² 7.979 1/0 119 93 0.387 448.0
70 mm² 9.441 2/0 151 118 0.268 627.2
95 mm² 10.998 3/0 182 142 0.193 851.2
120 mm² 12.361 250 kcmil 210 164 0.153 1075.2
150 mm² 13.82 300 kcmil 240 189 0.124 1344.0
185 mm² 15.348 350 kcmil 273 215 0.0991 1657.6
240 mm² 17.481 500 kcmil 321 252 0.0754 2150.4
300 mm² 19.544 600 kcmil 367 289 0.0601 2688.0

Copper ampacity: IEC 60364-5-52 method A1 (PVC insulation, conduit in an insulated wall, two loaded conductors, 30°C); 0.5–1.0 mm² are BS 7671 flexible-cord ratings. Resistance: IEC 60228 class 2 maximum at 20°C. Above 95 mm² the closest North American sizes are kcmil, not AWG.

Frequently Asked Questions

What is the metric equivalent of 12 AWG wire?

12 AWG (3.31 mm²) is closest to the IEC standard 2.5 mm² size, though 2.5 mm² is slightly smaller. The next metric size up is 4 mm², which exceeds 12 AWG. For an exact match, use the AWG to mm² conversion table.

What is 2.5 mm² wire used for?

2.5 mm² wire (roughly equivalent to 13 AWG) is the standard size for 20A outlet circuits in European and international wiring. It has an ampacity of approximately 20A and is used for kitchen, bathroom, and general-purpose circuits under IEC standards.

How does IEC 60228 differ from AWG?

IEC 60228 specifies wire sizes in mm² (cross-sectional area), while AWG uses an arbitrary gauge number where higher numbers mean smaller wire. IEC sizes are intuitive: larger mm² = larger wire. Standard IEC sizes: 0.5, 0.75, 1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300 mm².

Related

Wire types and insulation ratings → NEC Table 310.16 — conductor ampacity → mm² to AWG converter →