50 mm² Wire

50 mm² metric wire specifications (IEC 60228): 7.979 mm diameter, 119A ampacity (copper, IEC 60364-5-52 method A1, PVC, 2 loaded), closest AWG equivalent is 1/0. Resistance, weight, and common uses.

Size
50 mm²
IEC 60228
Diameter
7.979 mm
Ampacity (Cu)
119A
≈ AWG
1/0

50 mm² — Complete Specifications

Cross-sectional area50 mm²
Diameter (solid equivalent)7.979 mm
Closest AWG equivalent1/0 AWG
Ampacity (copper, IEC 60364-5-52 method A1, PVC, 2 loaded)119 A
Ampacity (aluminum)93 A
Max resistance (copper, 20°C, IEC 60228 class 2)0.387 Ω/km
Max resistance (aluminium, 20°C, IEC 60228)0.641 Ω/km
Weight (copper)448.0 kg/km
Weight (aluminum)135.0 kg/km

Common Uses for 50 mm² Wire

Metric vs AWG

The IEC 60228 metric system specifies wire by cross-sectional area in mm², while AWG uses a gauge number system. The closest AWG equivalent to 50 mm² is 1/0 AWG, but they are not exactly the same size.

Metric sizes are standard in Europe, Asia, Australia, and most countries outside North America. When replacing or matching wire between systems, always verify the actual cross-sectional area rather than relying on approximate equivalents.

Frequently Asked Questions

What is 50 mm² wire used for?

50 mm² metric wire (IEC 60228) is rated 119A (copper, IEC 60364-5-52 method A1, PVC, 2 loaded) and is commonly used for heavy industrial loads, main distribution cables, large three-phase motors. Its diameter is 7.979 mm. The closest AWG equivalent is 1/0 AWG.

What AWG gauge is equivalent to 50 mm²?

50 mm² wire is approximately equivalent to 1/0 AWG in the American Wire Gauge system. Note that IEC and AWG sizes do not align exactly — when substituting, choose the AWG size with equal or greater cross-sectional area to ensure adequate ampacity.

Explore

Wire types and insulation ratings → All metric wire sizes → 1/0 AWG specifications → AWG to mm² converter → Wire size calculator →
← 35 mm² 70 mm² →