Wire sizing rules change with the application: building wiring follows the NEC, boats follow ABYC E-11, and low-voltage DC and audio runs are usually limited by voltage drop long before ampacity. Each guide covers the governing standard, recommended gauges and practical tips.
14 AWG copper for 15A lighting, 12 AWG for 20A outlets, 10 AWG for 30A dryers and water heaters, with NM-B limited to the 60°C column.
Size 12V wire by current and the full round-trip length: a 20A load 10 feet from the battery needs 8 AWG to stay under 3% drop.
PV conductors must carry 156% of module Isc (NEC 690.8); most residential strings use 10 AWG PV wire, upsized for long home runs.
ABYC E-11 requires stranded copper and limits voltage drop to 3% for critical circuits and 10% for others; tinned boat cable is standard.
Keep wire resistance under 5% of speaker impedance: for 8Ω, 16 AWG to about 50 feet, 14 AWG to 80 feet, 12 AWG to 125 feet.
EV chargers are continuous loads: a 40A charger needs a 50A circuit and a 48A charger a 60A circuit, sized at 125% (NEC 625.41).
| Application | Standard | Key sizing rule | Voltage-drop target |
|---|---|---|---|
| Home wiring | NEC | Table 310.16 + 240.4(D) limits | 3% branch, 5% total (recommended) |
| EV charging | NEC 625 | Circuit at 125% of charger current | 3% |
| Solar PV | NEC 690 | 156% of module Isc | 1–2% (industry practice) |
| Marine | ABYC E-11 | Stranded copper, ABYC ampacity tables | 3% critical, 10% other |
| Automotive | SAE J1128 | Current and round-trip length | About 3% (common practice) |
| Speaker wire | None (not a code item) | Resistance under 5% of impedance | — |