Grounding Conductor Sizing

Two NEC tables cover grounding: Table 250.122 sizes the equipment grounding conductor (EGC) by the overcurrent device rating, and Table 250.66 sizes the grounding electrode conductor (GEC) by the largest service or feeder conductor.

Table 250.122 — Equipment Grounding Conductor (EGC)

OCPD Rating (A) Copper EGC Aluminum EGC
1514 AWG12 AWG
2012 AWG10 AWG
6010 AWG8 AWG
1008 AWG6 AWG
2006 AWG4 AWG
3004 AWG2 AWG
4003 AWG1 AWG
5002 AWG1/0 AWG
6001 AWG2/0 AWG
8001/0 AWG3/0 AWG
10002/0 AWG4/0 AWG
12003/0 AWG250 kcmil
16004/0 AWG350 kcmil
2000250 kcmil400 kcmil
2500350 kcmil600 kcmil
3000400 kcmil600 kcmil
4000500 kcmil750 kcmil
5000700 kcmil1250 kcmil
6000800 kcmil1250 kcmil
Where the overcurrent device is between listed sizes, use the next higher row. For parallel conductors, the EGC in each raceway must be sized based on the trip rating of the overcurrent device protecting the circuit.

Table 250.66 — Grounding Electrode Conductor (GEC)

Largest Cu Service Conductor Largest Al Service Conductor Cu GEC Al GEC
2 AWG or smaller1/0 AWG or smaller8 AWG6 AWG
1 or 1/0 AWG2/0 or 3/0 AWG6 AWG4 AWG
2/0 or 3/0 AWG4/0 AWG or 250 kcmil4 AWG2 AWG
Over 3/0 AWG – 350 kcmilOver 250 – 500 kcmil2 AWG1/0 AWG
Over 350 – 600 kcmilOver 500 – 900 kcmil1/0 AWG3/0 AWG
Over 600 – 1100 kcmilOver 900 – 1750 kcmil2/0 AWG4/0 AWG
Over 1100 kcmilOver 1750 kcmil3/0 AWG250 kcmil