Two independent derating factors reduce conductor ampacity: (1) ambient temperature above 30°C and (2) more than three current-carrying conductors in a raceway or cable. Apply both when both conditions exist.
| Temp (°C) | Temp (°F) | 60°C insulation | 75°C insulation | 90°C insulation |
|---|---|---|---|---|
| ≤10 | ≤50 | 1.29 | 1.2 | 1.15 |
| 11–15 | 51–59 | 1.22 | 1.15 | 1.12 |
| 16–20 | 60–68 | 1.15 | 1.11 | 1.08 |
| 21–25 | 69–77 | 1.08 | 1.05 | 1.04 |
| 26–30 | 78–86 | 1.0 | 1.0 | 1.0 |
| 31–35 | 87–95 | 0.91 | 0.94 | 0.96 |
| 36–40 | 96–104 | 0.82 | 0.88 | 0.91 |
| 41–45 | 105–113 | 0.71 | 0.82 | 0.87 |
| 46–50 | 114–122 | 0.58 | 0.75 | 0.82 |
| 51–55 | 123–131 | 0.41 | 0.67 | 0.76 |
| 56–60 | 132–140 | — | 0.58 | 0.71 |
| 61–65 | 141–149 | — | 0.47 | 0.65 |
| 66–70 | 150–158 | — | 0.33 | 0.58 |
| 71–75 | 159–167 | — | — | 0.5 |
| 76–80 | 168–176 | — | — | 0.41 |
| 81–85 | 177–185 | — | — | 0.29 |
| Current-Carrying Conductors | Adjustment Factor (%) |
|---|---|
| 4–6 | 80% |
| 7–9 | 70% |
| 10–20 | 50% |
| 21–30 | 45% |
| 31–40 | 40% |
| 41–& above | 35% |
When both conditions apply, multiply the table ampacity by both factors:
Derated ampacity = Table ampacity × temperature factor × bundle factor
Example: 12 AWG THHN (90°C column = 30 A) at 40°C ambient with 6 current-carrying conductors: 30 × 0.91 × 0.80 = 21.8 A
WireSizing.com is an independent reference. NEC® is a registered trademark of the NFPA. Values shown are commonly published engineering data; always confirm against the edition adopted in your jurisdiction and consult a licensed electrician.