NEC Tables 430.247 through 430.250 list the full-load current used to size conductors, overload protection and short-circuit protection for motors. These are not nameplate values — they are the Code’s design figures for worst-case normal operation.
The NEC uses these table values — not the motor nameplate — to size branch-circuit conductors (125% of the table FLA per 430.22), overload protection (based on actual nameplate), and short-circuit / ground-fault protection (varies by motor type per Table 430.52).
For multi-motor circuits, size the feeder for the sum of all motor FLAs plus 25% of the largest motor (430.24).
WireSizing.com is an independent reference. NEC® is a registered trademark of the NFPA. Values shown are commonly published engineering data; always confirm against the edition adopted in your jurisdiction and consult a licensed electrician.