WireSizing
Wire gauge reference & calculator

25 HP Motor — Full-Load Amps

Full-load ampere values for a 25-horsepower motor at every standard voltage and phase configuration listed in the NEC.

Three-Phase Induction (Table 430.250)

Voltage Full-Load Amps
115 V—
200 V78.2
208 V74.8
230 V68
460 V34
575 V27
2300 V—

DC (Table 430.247)

Voltage Full-Load Amps
90 V—
120 V—
180 V—
240 V89
500 V43
550 V38

Two-Phase 4-Wire (Table 430.249)

Voltage Full-Load Amps
115 V—
230 V59
460 V29
575 V24
2300 V—
← 20 HP 30 HP →

Frequently Asked Questions

How many amps does a 25 HP motor draw?

The NEC tables list the full-load current for a 25 HP motor at each standard voltage and phase configuration. These are design values for sizing conductors and protection, not nameplate ratings. See the table above for all voltages.

What size wire do I need for a 25 HP motor?

Size the branch-circuit conductors at 125% of the table FLA (NEC 430.22). Look up the FLA for your voltage above, multiply by 1.25, then find that ampacity in the wire size tables.

Related

← All motor FLA tables AWG wire chart → Breaker size charts →

WireSizing.com is an independent reference. NEC® is a registered trademark of the NFPA. Values shown are commonly published engineering data; always confirm against the edition adopted in your jurisdiction and consult a licensed electrician.