The NEC mandates colors only for the grounded conductor (neutral = white or gray, NEC 200.6) and the equipment grounding conductor (green or green/yellow, NEC 250.119). All other colors are convention, but the industry follows them consistently.
| Function | Color | Notes |
|---|---|---|
| Line (hot) | Black | L1 — ungrounded conductor |
| Line 2 (hot) | Red | L2 in 240V split-phase |
| Neutral | White | Grounded conductor — NEC 200.6 required |
| Ground | Green / bare | Equipment grounding — NEC 250.119 required |
| Function | Color |
|---|---|
| Phase A | Black |
| Phase B | Red |
| Phase C | Blue |
| Neutral | White |
| Ground | Green / bare |
| Function | Color |
|---|---|
| Phase A | Brown |
| Phase B | Orange |
| Phase C | Yellow |
| Neutral | Gray |
| Ground | Green / bare |
| Positive (+) | Red |
| Negative (−) | Black |
| Ground | Green / bare |
WireSizing.com is an independent reference. NEC® is a registered trademark of the NFPA. Values shown are commonly published engineering data; always confirm against the edition adopted in your jurisdiction and consult a licensed electrician.