WireSizing
Wire gauge reference & calculator

Wire Gauge Reference & Calculator

Find the right wire size for any circuit. AWG & metric charts with ampacity, resistance, and diameter. Based on NEC and IEC standards.

44 AWG sizes NEC ampacity tables AWG & metric Voltage drop calculator

Popular Wire Sizes

Copper ampacity at 60 °C (NM-B / romex). See individual pages for 75 °C and 90 °C ratings.

4/0 AWG
195A
11.684 mm · 107.2193 mm²
2/0 AWG
145A
9.2658 mm · 67.4309 mm²
1/0 AWG
125A
8.2515 mm · 53.4751 mm²
2 AWG
95A
6.5437 mm · 33.6308 mm²
4 AWG
70A
5.1894 mm · 21.1506 mm²
6 AWG
55A
4.1154 mm · 13.3018 mm²
8 AWG
40A
3.2636 mm · 8.3656 mm²
10 AWG
30A
2.5882 mm · 5.2612 mm²
12 AWG
20A
2.0525 mm · 3.3088 mm²
14 AWG
15A
1.6277 mm · 2.0809 mm²

Wire Size by Amperage

15A Circuit
14 AWG
Copper · Standard lighting and outlet c
20A Circuit
12 AWG
Copper · Kitchen, bathroom, garage circ
30A Circuit
10 AWG
Copper · Dryers, water heaters, small A
40A Circuit
8 AWG
Copper · Electric ranges, large AC unit
50A Circuit
6 AWG
Copper · Ranges, hot tubs, EV chargers,
60A Circuit
6 AWG
Copper · Sub-panels, large EV chargers,
70A Circuit
4 AWG
Copper · Large sub-panels, commercial e
80A Circuit
4 AWG
Copper · Large sub-panels, industrial f
View all amperage lookups →

Conduit Fill & NEC Reference

Conduit Fill Charts
EMT, PVC, rigid & IMC · 1/2″ to 4″
Conduit Fill Calculator
Check any pull against NEC Chapter 9
Circuit Breaker Size Chart
Wire & ground size for 15A to 200A
Wire Types
THHN, Romex, XHHW, UF-B, USE-2
NEC Table Reference
310.16, 310.15, 250.66, 250.122, 300.5
Voltage Drop Formula
VD = 2 × I × R × L ÷ 1000

Appliance Wiring Guides

Electric Dryer
10 AWG · 30A double-pole
Electric Water Heater
10 AWG · 30A double-pole
Electric Range / Stove
6 AWG · 50A double-pole
Central Air Conditioner
10 AWG · 30A double-pole
Hot Tub / Spa
6 AWG · 50A double-pole GFCI
EV Charger (Level 2)
6 AWG · 50A double-pole
Well Pump
12 AWG · 20A double-pole
Welder
6 AWG · 50A double-pole
View all appliance guides →

How WireSizing Works

Calculated from Standards

All wire data calculated from the AWG formula (ASTM B258), material resistivities, and NEC/IEC ampacity standards.

Complete Reference

Every AWG size from 4/0 to 40, all 19 IEC metric sizes, 8 conductor materials, and NEC ampacity at 60/75/90°C.

Practical Guides

Appliance wiring guides with NEC references, breaker sizes, and wire types. Real-world sizing for dryers, hot tubs, EV chargers, and more.

Frequently Asked Questions

What wire size do I need for a 20-amp circuit?

For a 20-amp circuit, use 12 AWG copper wire (or 10 AWG aluminum). This is the NEC-required minimum for kitchen, bathroom, and garage circuits.

How do I calculate voltage drop for a long wire run?

Voltage drop = (2 × length × amps × resistance per foot). NEC recommends keeping voltage drop under 3% for branch circuits. Use our free calculator — enter amps, voltage, distance, and wire gauge to get the exact percentage.

What is AWG and how does it work?

AWG (American Wire Gauge) is the US standard for wire size. Counterintuitively, larger AWG numbers mean thinner wire: 14 AWG is thinner than 10 AWG. Common household sizes: 14 AWG (15A), 12 AWG (20A), 10 AWG (30A), 8 AWG (40A), 6 AWG (55A).