Electric Dryer — Wire Size & Circuit Requirements

Standard electric dryers draw 22-24 amps and require a dedicated 30-amp, 240-volt circuit.

Wire Size
10 AWG
Breaker
30A double-pole
Voltage
240V
Circuit Breaker
30A

Wiring Specifications

Recommended wire10/3 NM-B or 10 AWG THHN
Breaker30A double-pole
Voltage240V
Typical amperage22–24A
Circuit amperage30A
NEC referenceNEC 220.54
Max recommended distanceAbout 120 feet one-way for 3% drop at 24A

Important Notes

A 4-wire connection (10/3 with ground) is required by current code. Older 3-wire connections (10/2) may exist but should not be used for new installations.

Frequently Asked Questions

What wire size for an electric dryer?

10 AWG copper wire on a 30A double-pole, 240V breaker. Standard electric dryers draw 22–24 amps. NEC 250.140 requires a 4-wire connection (two hots, neutral, ground) for all new dryer installations.

Does an electric dryer need a dedicated circuit?

Yes — electric dryers must have a dedicated 30A, 240V circuit. No other loads can share this circuit. The dryer cord connects to a 3-slot or 4-slot dryer outlet (NEMA 10-30 or 14-30).

Can I use 12 AWG wire for a dryer?

No — 12 AWG is undersized for a dryer circuit. Electric dryers draw 22–24 amps and require 10 AWG copper wire on a 30A breaker. Using 12 AWG wire on a 30A breaker is a code violation and fire hazard.

What is the difference between a 3-wire and 4-wire dryer connection?

Older homes have 3-wire dryer outlets (NEMA 10-30) with two hots and a neutral. Current NEC code requires 4-wire connections (NEMA 14-30) with two hots, a neutral, and a separate ground wire. All new dryer installations must use 4-wire connections per NEC 250.140.

Related

Circuit breaker size chart → NEC Table 250.122 — ground wire size → Romex (NM-B) cable → 10 AWG specifications → Wire size for 30A circuits → Wire size calculator → All appliance guides →