10 AWG Wire

10 AWG (American Wire Gauge) wire specifications: 2.5882 mm diameter, 5.2612 mm² area, 35A ampacity (copper, 75°C), protected at 30A max per NEC 240.4(D). Resistance, weight, and common uses.

Diameter
2.5882 mm
0.101897"
Area
5.2612 mm²
10,383 cmil
Ampacity (Cu)
35A
75°C · 30A breaker max
Resistance (Cu)
3.2768
Ω/km at 20°C
Breaker limit: 10 AWG copper is rated 35A at 75°C in NEC Table 310.16, but NEC 240.4(D) limits the overcurrent device to 30A (25A for 10 AWG aluminum). Size the breaker to 30A, not 35A. See wire size for 30 amps.

10 AWG — Complete Specifications

Diameter2.5882 mm · 0.101897" · 101.9 mils
Cross-sectional area5.2612 mm² · 10,383 circular mils
Resistance (copper, 20°C)3.2768 Ω/km · 0.9988 Ω/1000ft
Resistance (aluminum, 20°C)5.3718 Ω/km · 1.6373 Ω/1000ft
Ampacity — copper 60°C30 A
Ampacity — copper 75°C35 A
Ampacity — copper 90°C40 A
Ampacity — aluminum 75°C30 A
Weight (copper)47.14 kg/km · 31.677 lbs/1000ft
Weight (aluminum)14.205 kg/km · 9.545 lbs/1000ft
Closest IEC 60228 size6 mm²
Skin depth at 60 Hz8.531 mm

Common Uses for 10 AWG Wire

Compatible Insulation Types

TypeTemperatureDescription
THHN/THWN-2 90°C dry / 75°C wet Most common for building wire
XHHW-2 90°C dry and wet Cross-linked polyethylene, moisture resistant
USE-2 90°C Underground service entrance
NM-B (Romex) 90°C Non-metallic sheathed cable for residential
UF-B 60°C Underground feeder, direct burial

Frequently Asked Questions

What is 10 AWG wire used for?

10 AWG copper is commonly used for 30A circuits such as electric dryers and water heaters. NEC Table 310.16 rates it 35A at 75°C, but NEC 240.4(D) limits the breaker or fuse protecting it to 30A, which is why it is the standard wire for 30A circuits. It measures 2.588 mm in diameter with a 5.26 mm² cross-section.

What is the ampacity of 10 AWG wire?

Per NEC Table 310.16 (30°C ambient, no more than three current-carrying conductors), 10 AWG copper is rated 30A at 60°C, 35A at 75°C and 40A at 90°C. 10 AWG aluminum is rated 25A, 30A and 35A in the same columns. Regardless of those ratings, NEC 240.4(D) caps overcurrent protection at 30A for copper and 25A for aluminum. On circuits of 100A or less, NEC 110.14(C) generally requires the 60°C column unless every termination is rated 75°C.

Is 10 AWG wire available in aluminum?

Yes, but it is uncommon for new work. 10 AWG aluminum is rated 30A at 75°C, and NEC 240.4(D) limits it to a 25A breaker. Small-gauge aluminum branch wiring from the 1960s–70s is known for overheating at connections, so any device on it must be rated CO/ALR or AL/CU, or pigtailed with approved connectors.