9 AWG Wire

9 AWG (American Wire Gauge) wire specifications: 2.9064 mm diameter, 6.6342 mm² area. Resistance, weight, and common uses.

Diameter
2.9064 mm
0.114424"
Area
6.6342 mm²
13,093 cmil
Ampacity (Cu)
—
75°C insulation
Resistance (Cu)
2.5987
Ω/km at 20°C

9 AWG — Complete Specifications

Diameter2.9064 mm · 0.114424" · 114.42 mils
Cross-sectional area6.6342 mm² · 13,093 circular mils
Resistance (copper, 20°C)2.5987 Ω/km · 0.7921 Ω/1000ft
Resistance (aluminum, 20°C)4.2602 Ω/km · 1.2985 Ω/1000ft
Ampacity — copper 60°C— A
Ampacity — copper 75°C— A
Ampacity — copper 90°C— A
Ampacity — aluminum 75°C— A
Weight (copper)59.442 kg/km · 39.943 lbs/1000ft
Weight (aluminum)17.912 kg/km · 12.037 lbs/1000ft
Closest IEC 60228 size6 mm²
Skin depth at 60 Hz8.531 mm

Common Uses for 9 AWG Wire

Compatible Insulation Types

TypeTemperatureDescription
THHN/THWN-2 90°C dry / 75°C wet Most common for building wire
XHHW-2 90°C dry and wet Cross-linked polyethylene, moisture resistant
USE-2 90°C Underground service entrance
NM-B (Romex) 90°C Non-metallic sheathed cable for residential
UF-B 60°C Underground feeder, direct burial

Frequently Asked Questions

What is 9 AWG wire used for?

9 AWG copper (2.906 mm diameter, 6.63 mm²) is uncommon in commercial wiring. It occasionally appears in thermocouple extension wire, industrial temperature-sensing circuits, and older European-manufactured equipment adapted for North American use. Most designs use 10 AWG or 8 AWG instead.

What is the ampacity of 9 AWG wire?

Per NEC Table 310.16, 9 AWG copper is rated 30 A at 60°C, 35 A at 75°C, and 40 A at 90°C. NEC 240.4(D) does not list 9 AWG among the sizes with fixed breaker limits (those are 14, 12, and 10 only), so overcurrent protection follows the general rules of NEC 240.4(B).