WireSizing
Wire gauge reference & calculator

6 mm² Wire

6 mm² metric wire specifications (IEC 60228): 2.764 mm diameter, 34A ampacity (copper, IEC 60364-5-52 method A1, PVC, 2 loaded), closest AWG equivalent is 9. Resistance, weight, and common uses.

Size
6 mm²
IEC 60228
Diameter
2.764 mm
Ampacity (Cu)
34A
≈ AWG
9

6 mm² — Complete Specifications

Cross-sectional area6 mm²
Diameter (solid equivalent)2.764 mm
Closest AWG equivalent9 AWG
Ampacity (copper, IEC 60364-5-52 method A1, PVC, 2 loaded)34 A
Ampacity (aluminum)27 A
Max resistance (copper, 20°C, IEC 60228 class 2)3.08 Ω/km
Max resistance (aluminium, 20°C, IEC 60228)— (IEC 60228 aluminium starts at 10 mm²)
Weight (copper)53.76 kg/km
Weight (aluminum)16.2 kg/km

Common Uses for 6 mm² Wire

Metric vs AWG

The IEC 60228 metric system specifies wire by cross-sectional area in mm², while AWG uses a gauge number system. The closest AWG equivalent to 6 mm² is 9 AWG, but they are not exactly the same size.

Metric sizes are standard in Europe, Asia, Australia, and most countries outside North America. When replacing or matching wire between systems, always verify the actual cross-sectional area rather than relying on approximate equivalents.

Frequently Asked Questions

What is 6 mm² wire used for?

6 mm² metric wire (IEC 60228) is rated 34A (copper, IEC 60364-5-52 method A1, PVC, 2 loaded) and is commonly used for electric cooktops, large water heaters, small air conditioners. Its diameter is 2.764 mm. The closest AWG equivalent is 9 AWG.

What AWG gauge is equivalent to 6 mm²?

6 mm² wire is approximately equivalent to 9 AWG in the American Wire Gauge system. Note that IEC and AWG sizes do not align exactly — when substituting, choose the AWG size with equal or greater cross-sectional area to ensure adequate ampacity.

Explore

Wire types and insulation ratings → All metric wire sizes → 9 AWG specifications → AWG to mm² converter → Wire size calculator →
← 4 mm² 10 mm² →