WireSizing
Wire gauge reference & calculator

Electrical Box Fill — NEC 314.16

NEC 314.16 limits the number of conductors, devices and fittings in a box based on the box’s volume in cubic inches. Each item type counts differently.

Volume Allowance per Conductor

Wire Size (AWG) Volume per Conductor (in³)
6 AWG5.0
8 AWG3.0
10 AWG2.5
12 AWG2.25
14 AWG2.0
16 AWG1.75
18 AWG1.5

Standard Box Volumes (Table 314.16(A))

Box Dimensions Shape Volume (in³)
4 × 1-1/4Round / octagonal12.5
4 × 1-1/2Round / octagonal15.5
4 × 2-1/8Round / octagonal21.5
4 × 1-1/4Square18.0
4 × 1-1/2Square21.0
4 × 2-1/8Square30.3
4-11/16 × 1-1/4Square25.5
4-11/16 × 1-1/2Square29.5
4-11/16 × 2-1/8Square42.0
3 × 2 × 1-1/2Device7.5
3 × 2 × 2Device10.0
3 × 2 × 2-1/4Device10.5
3 × 2 × 2-1/2Device12.5
3 × 2 × 2-3/4Device14.0
3 × 2 × 3-1/2Device18.0
4 × 2-1/8 × 1-1/2Device10.3
4 × 2-1/8 × 1-7/8Device13.0
4 × 2-1/8 × 2-1/8Device14.5
3-3/4 × 2 × 2-1/2Masonry14.0
3-3/4 × 2 × 3-1/2Masonry21.0

How to Count Box Fill (NEC 314.16(B))

Related

Conduit fill charts → Grounding conductor sizing → AWG wire chart →

WireSizing.com is an independent reference. NEC® is a registered trademark of the NFPA. Values shown are commonly published engineering data; always confirm against the edition adopted in your jurisdiction and consult a licensed electrician.