8 AWG Wire

8 AWG (American Wire Gauge) wire specifications: 3.2636 mm diameter, 8.3656 mm² area, 50A ampacity (copper, 75°C). Resistance, weight, and common uses.

Diameter
3.2636 mm
0.12849"
Area
8.3656 mm²
16,510 cmil
Ampacity (Cu)
50A
75°C insulation
Resistance (Cu)
2.0608
Ω/km at 20°C

8 AWG — Complete Specifications

Diameter3.2636 mm · 0.12849" · 128.49 mils
Cross-sectional area8.3656 mm² · 16,510 circular mils
Resistance (copper, 20°C)2.0608 Ω/km · 0.6281 Ω/1000ft
Resistance (aluminum, 20°C)3.3784 Ω/km · 1.0297 Ω/1000ft
Ampacity — copper 60°C40 A
Ampacity — copper 75°C50 A
Ampacity — copper 90°C55 A
Ampacity — aluminum 75°C40 A
Weight (copper)74.955 kg/km · 50.368 lbs/1000ft
Weight (aluminum)22.587 kg/km · 15.178 lbs/1000ft
Closest IEC 60228 size10 mm²
Skin depth at 60 Hz8.531 mm

Common Uses for 8 AWG Wire

Compatible Insulation Types

TypeTemperatureDescription
THHN/THWN-2 90°C dry / 75°C wet Most common for building wire
XHHW-2 90°C dry and wet Cross-linked polyethylene, moisture resistant
USE-2 90°C Underground service entrance
NM-B (Romex) 90°C Non-metallic sheathed cable for residential
UF-B 60°C Underground feeder, direct burial

Frequently Asked Questions

What is 8 AWG wire used for?

8 AWG copper is commonly used for 40–50A circuits such as ranges, cooktops and larger AC condensers. NEC Table 310.16 rates it 50A at 75°C. It measures 3.264 mm in diameter with a 8.37 mm² cross-section.

What is the ampacity of 8 AWG wire?

Per NEC Table 310.16 (30°C ambient, no more than three current-carrying conductors), 8 AWG copper is rated 40A at 60°C, 50A at 75°C and 55A at 90°C. 8 AWG aluminum is rated 35A, 40A and 45A in the same columns. On circuits of 100A or less, NEC 110.14(C) generally requires the 60°C column unless every termination is rated 75°C.

Is 8 AWG wire available in aluminum?

Yes. 8 AWG aluminum is rated 40A at 75°C versus 50A for copper, so matching the copper rating takes 6 AWG aluminum. Aluminum at this size is common for feeders, subpanels and service conductors (SER, USE-2, XHHW-2). Use AL-rated lugs, torque to the manufacturer’s spec and apply antioxidant compound where required.

8 AWG voltage drop by distance

Circuits that use 8 AWG copper