8 AWG Wire for 75 Feet

Voltage drop analysis for 8 AWG copper wire over a 75-foot one-way run. See whether this gauge is suitable for your circuit at various loads and voltages.

Wire
8 AWG
Distance
75 ft
Resistance
0.6281
Ω/1000ft

Voltage Drop at 75 Feet

Single phase, copper conductor, one-way distance. ✅ = under 3%, ⚠️ = 3-5%, ❌ = over 5%

Load V-Drop @ 120V @ 240V
15A 1.41V ✅ 1.2% ✅ 0.6%
20A 1.88V ✅ 1.6% ✅ 0.8%
30A 2.83V ✅ 2.4% ✅ 1.2%
40A 3.77V ⚠️ 3.1% ✅ 1.6%
50A 4.71V ⚠️ 3.9% ✅ 2.0%

How Voltage Drop Is Calculated

Voltage drop for single-phase circuits: Vdrop = 2 × I × R × L

Where I = current in amps, R = resistance per foot (0.000628 Ω/ft for 8 AWG copper), and L = one-way distance (75 ft).

The factor of 2 accounts for both the supply and return conductors. NEC recommends a maximum 3% voltage drop for branch circuits and 5% for the total circuit (feeder + branch).

If voltage drop is too high: Use the next larger wire size. Going from 8 to 7 AWG roughly halves the voltage drop. Alternatively, for 120V loads, consider rewiring for 240V — same absolute drop but half the percentage.