4 AWG Wire for 75 Feet

Over 75 feet one-way, 4 AWG copper drops 1.5% at 40A on 120V and 1.5% at 80A on 240V: loads up to 70A stay under 3% at 120V, and every load here up to 80A stays under 3% at 240V.

Wire
4 AWG
Distance
75 ft
Resistance
0.308
Ω/1000ft at 75°C

Voltage Drop at 75 Feet

Single phase, copper conductor, one-way distance. ✅ = under 3%, ⚠️ = 3-5%, ❌ = over 5%

Load V-Drop @ 120V @ 240V
40A 1.8V ✅ 1.5% ✅ 0.8%
50A 2.3V ✅ 1.9% ✅ 1.0%
60A 2.8V ✅ 2.3% ✅ 1.2%
70A 3.2V ✅ 2.7% ✅ 1.3%
80A* 3.7V ⚠️ 3.1% ✅ 1.5%

Maximum 4 AWG Run for 3% Drop

Longest one-way distance that keeps single-phase copper within 3%.

Load @ 120V @ 240V
40A 145 ft 290 ft
50A 115 ft 235 ft
60A 95 ft 195 ft
70A 85 ft 165 ft
80A 75 ft 145 ft

* Above 70A, 4 AWG needs 75°C-rated terminations at both ends (NEC 110.14(C)); most breakers and panels rated 100A or less assume 60°C unless marked 75°C.

How Voltage Drop Is Calculated

Voltage drop for single-phase circuits: Vdrop = 2 × I × R × L

Where I = current in amps, R = resistance per foot (0.000308 Ω/ft for 4 AWG copper, from NEC Chapter 9 Table 8 at 75°C), and L = one-way distance (75 ft).

The factor of 2 accounts for both the supply and return conductors. NEC recommends a maximum 3% voltage drop for branch circuits and 5% for the total circuit (feeder + branch).

If voltage drop is too high: Use the next larger wire size. Each single AWG step up in size cuts voltage drop by about 21% — it takes three steps to roughly halve it, since each step increases the conductor area by a factor of 1.26. Alternatively, for 120V loads, consider rewiring for 240V — same absolute drop but half the percentage.

Frequently Asked Questions

Can I use 4 AWG wire for a 75-foot run?

It depends on the load and voltage. With NEC Table 8 resistance (0.308 Ω per 1000 ft at 75°C), a 75-foot run of 4 AWG copper drops 1.5% at 40A, 1.9% at 50A, 2.3% at 60A, 2.7% at 70A, 3.1% at 80A on 120V, and half those percentages on 240V. All of these meet the 3% branch-circuit guideline at 240V.

How far can you run 4 AWG wire?

To stay within 3% voltage drop, 4 AWG copper can run about 145 ft at 40A on 120V, or 145 ft at 80A on 240V (one-way). Its maximum load is 85A at 75°C; lighter loads can run proportionally farther.

When should I upsize from 4 AWG over 75 feet?

Upsize when your load pushes drop above 3%. At 80A on 240V over 75 feet, 4 AWG drops 1.5%; stepping up to 3 AWG cuts that to 1.2%. For motors, well pumps or sensitive electronics, aim for 2% or less.