4 AWG Wire for 200 Feet

Over 200 feet one-way, 4 AWG copper drops 4.1% at 40A on 120V and 4.1% at 80A on 240V: no load in this table stays under 3% at 120V, and loads up to 50A stay under 3% at 240V.

Wire
4 AWG
Distance
200 ft
Resistance
0.308
Ω/1000ft at 75°C

Voltage Drop at 200 Feet

Single phase, copper conductor, one-way distance. ✅ = under 3%, ⚠️ = 3-5%, ❌ = over 5%

Load V-Drop @ 120V @ 240V
40A 4.9V ⚠️ 4.1% ✅ 2.1%
50A 6.2V ❌ 5.1% ✅ 2.6%
60A 7.4V ❌ 6.2% ⚠️ 3.1%
70A 8.6V ❌ 7.2% ⚠️ 3.6%
80A* 9.9V ❌ 8.2% ⚠️ 4.1%

Maximum 4 AWG Run for 3% Drop

Longest one-way distance that keeps single-phase copper within 3%.

Load @ 120V @ 240V
40A 145 ft 290 ft
50A 115 ft 235 ft
60A 95 ft 195 ft
70A 85 ft 165 ft
80A 75 ft 145 ft

* Above 70A, 4 AWG needs 75°C-rated terminations at both ends (NEC 110.14(C)); most breakers and panels rated 100A or less assume 60°C unless marked 75°C.

How Voltage Drop Is Calculated

Voltage drop for single-phase circuits: Vdrop = 2 × I × R × L

Where I = current in amps, R = resistance per foot (0.000308 Ω/ft for 4 AWG copper, from NEC Chapter 9 Table 8 at 75°C), and L = one-way distance (200 ft).

The factor of 2 accounts for both the supply and return conductors. NEC recommends a maximum 3% voltage drop for branch circuits and 5% for the total circuit (feeder + branch).

If voltage drop is too high: Use the next larger wire size. Each single AWG step up in size cuts voltage drop by about 21% — it takes three steps to roughly halve it, since each step increases the conductor area by a factor of 1.26. Alternatively, for 120V loads, consider rewiring for 240V — same absolute drop but half the percentage.

Frequently Asked Questions

Can I use 4 AWG wire for a 200-foot run?

It depends on the load and voltage. With NEC Table 8 resistance (0.308 Ω per 1000 ft at 75°C), a 200-foot run of 4 AWG copper drops 4.1% at 40A, 5.1% at 50A, 6.2% at 60A, 7.2% at 70A, 8.2% at 80A on 120V, and half those percentages on 240V. At 240V, loads up to 50A meet the 3% guideline.

How far can you run 4 AWG wire?

To stay within 3% voltage drop, 4 AWG copper can run about 145 ft at 40A on 120V, or 145 ft at 80A on 240V (one-way). Its maximum load is 85A at 75°C; lighter loads can run proportionally farther.

When should I upsize from 4 AWG over 200 feet?

Upsize when your load pushes drop above 3%. At 80A on 240V over 200 feet, 4 AWG drops 4.1%; stepping up to 3 AWG cuts that to 3.3%. For motors, well pumps or sensitive electronics, aim for 2% or less.

Other distances for 4 AWG

Other gauges at 200 feet

Related

Voltage drop formula → 4 AWG full specifications → Wire size calculator → All distance charts →