WireSizing
Wire gauge reference & calculator

10 AWG Wire for 200 Feet

Over 200 feet one-way, 10 AWG copper drops 6.2% at 15A on 120V and 6.2% at 30A on 240V: no load in this table stays under 3% at 120V, and no load in this table stays under 3% at 240V.

Wire
10 AWG
Distance
200 ft
Resistance
1.24
Ω/1000ft at 75°C

Voltage Drop at 200 Feet

Single phase, copper conductor, one-way distance. ✅ = under 3%, ⚠️ = 3-5%, ❌ = over 5%

Load V-Drop @ 120V @ 240V
15A 7.4V ❌ 6.2% ⚠️ 3.1%
20A 9.9V ❌ 8.3% ⚠️ 4.1%
25A 12.4V ❌ 10.3% ❌ 5.2%
30A 14.9V ❌ 12.4% ❌ 6.2%

Maximum 10 AWG Run for 3% Drop

Longest one-way distance that keeps single-phase copper within 3%.

Load @ 120V @ 240V
15A 95 ft 195 ft
20A 75 ft 145 ft
25A 60 ft 115 ft
30A 50 ft 95 ft

How Voltage Drop Is Calculated

Voltage drop for single-phase circuits: Vdrop = 2 × I × R × L

Where I = current in amps, R = resistance per foot (0.00124 Ω/ft for 10 AWG copper, from NEC Chapter 9 Table 8 at 75°C), and L = one-way distance (200 ft).

The factor of 2 accounts for both the supply and return conductors. NEC recommends a maximum 3% voltage drop for branch circuits and 5% for the total circuit (feeder + branch).

If voltage drop is too high: Use the next larger wire size. Each single AWG step up in size cuts voltage drop by about 21% — it takes three steps to roughly halve it, since each step increases the conductor area by a factor of 1.26. Alternatively, for 120V loads, consider rewiring for 240V — same absolute drop but half the percentage.

Frequently Asked Questions

Can I use 10 AWG wire for a 200-foot run?

It depends on the load and voltage. With NEC Table 8 resistance (1.24 Ω per 1000 ft at 75°C), a 200-foot run of 10 AWG copper drops 6.2% at 15A, 8.3% at 20A, 10.3% at 25A, 12.4% at 30A on 120V, and half those percentages on 240V. None meet the 3% guideline, so a larger wire is needed.

How far can you run 10 AWG wire?

To stay within 3% voltage drop, 10 AWG copper can run about 95 ft at 15A on 120V, or 95 ft at 30A on 240V (one-way). Its maximum load is 30A (the NEC 240.4(D) limit); lighter loads can run proportionally farther.

When should I upsize from 10 AWG over 200 feet?

Upsize when your load pushes drop above 3%. At 30A on 240V over 200 feet, 10 AWG drops 6.2%; stepping up to 8 AWG cuts that to 3.9%. For motors, well pumps or sensitive electronics, aim for 2% or less.

Other distances for 10 AWG

Other gauges at 200 feet

Related

Voltage drop formula → 10 AWG full specifications → Wire size calculator → All distance charts →