WireSizing
Wire gauge reference & calculator

2/0 AWG Wire for 200 Feet

Voltage drop analysis for 2/0 AWG copper wire over a 200-foot one-way run. See whether this gauge is suitable for your circuit at various loads and voltages.

Wire
2/0 AWG
Distance
200 ft
Resistance
0.0779
Ω/1000ft

Voltage Drop at 200 Feet

Single phase, copper conductor, one-way distance. ✅ = under 3%, ⚠️ = 3-5%, ❌ = over 5%

Load V-Drop @ 120V @ 240V
15A 0.47V ✅ 0.4% ✅ 0.2%
20A 0.62V ✅ 0.5% ✅ 0.3%
30A 0.93V ✅ 0.8% ✅ 0.4%
40A 1.25V ✅ 1.0% ✅ 0.5%
50A 1.56V ✅ 1.3% ✅ 0.6%

How Voltage Drop Is Calculated

Voltage drop for single-phase circuits: Vdrop = 2 × I × R × L

Where I = current in amps, R = resistance per foot (0.000078 Ω/ft for 2/0 AWG copper), and L = one-way distance (200 ft).

The factor of 2 accounts for both the supply and return conductors. NEC recommends a maximum 3% voltage drop for branch circuits and 5% for the total circuit (feeder + branch).

If voltage drop is too high: Use the next larger wire size. Going from 2/0 to 3/0 AWG roughly halves the voltage drop. Alternatively, for 120V loads, consider rewiring for 240V — same absolute drop but half the percentage.

Related

2/0 AWG full specifications → Wire size calculator → All distance charts →