WireSizing
Wire gauge reference & calculator

2/0 AWG Wire for 150 Feet

Over 150 feet one-way, 2/0 AWG copper drops 2.4% at 100A on 120V and 2.1% at 175A on 240V: loads up to 100A stay under 3% at 120V, and every load here up to 175A stays under 3% at 240V.

Wire
2/0 AWG
Distance
150 ft
Resistance
0.0967
Ω/1000ft at 75°C

Voltage Drop at 150 Feet

Single phase, copper conductor, one-way distance. ✅ = under 3%, ⚠️ = 3-5%, ❌ = over 5%

Load V-Drop @ 120V @ 240V
100A 2.9V ✅ 2.4% ✅ 1.2%
125A 3.6V ⚠️ 3.0% ✅ 1.5%
150A 4.4V ⚠️ 3.6% ✅ 1.8%
175A 5.1V ⚠️ 4.2% ✅ 2.1%

Maximum 2/0 AWG Run for 3% Drop

Longest one-way distance that keeps single-phase copper within 3%.

Load @ 120V @ 240V
100A 185 ft 370 ft
125A 150 ft 300 ft
150A 125 ft 250 ft
175A 105 ft 215 ft

How Voltage Drop Is Calculated

Voltage drop for single-phase circuits: Vdrop = 2 × I × R × L

Where I = current in amps, R = resistance per foot (9.67e-05 Ω/ft for 2/0 AWG copper, from NEC Chapter 9 Table 8 at 75°C), and L = one-way distance (150 ft).

The factor of 2 accounts for both the supply and return conductors. NEC recommends a maximum 3% voltage drop for branch circuits and 5% for the total circuit (feeder + branch).

If voltage drop is too high: Use the next larger wire size. Each single AWG step up in size cuts voltage drop by about 21% — it takes three steps to roughly halve it, since each step increases the conductor area by a factor of 1.26. Alternatively, for 120V loads, consider rewiring for 240V — same absolute drop but half the percentage.

Frequently Asked Questions

Can I use 2/0 AWG wire for a 150-foot run?

It depends on the load and voltage. With NEC Table 8 resistance (0.0967 Ω per 1000 ft at 75°C), a 150-foot run of 2/0 AWG copper drops 2.4% at 100A, 3.0% at 125A, 3.6% at 150A, 4.2% at 175A on 120V, and half those percentages on 240V. All of these meet the 3% branch-circuit guideline at 240V.

How far can you run 2/0 AWG wire?

To stay within 3% voltage drop, 2/0 AWG copper can run about 185 ft at 100A on 120V, or 215 ft at 175A on 240V (one-way). Its maximum load is 175A at 75°C; lighter loads can run proportionally farther.

When should I upsize from 2/0 AWG over 150 feet?

Upsize when your load pushes drop above 3%. At 175A on 240V over 150 feet, 2/0 AWG drops 2.1%; stepping up to 3/0 AWG cuts that to 1.7%. For motors, well pumps or sensitive electronics, aim for 2% or less.

Other distances for 2/0 AWG

Other gauges at 150 feet

Related

Voltage drop formula → 2/0 AWG full specifications → Wire size calculator → All distance charts →