10 AWG Wire for 150 Feet

Over 150 feet one-way, 10 AWG copper drops 4.7% at 15A on 120V and 4.7% at 30A on 240V: no load in this table stays under 3% at 120V, and loads up to 15A stay under 3% at 240V.

Wire
10 AWG
Distance
150 ft
Resistance
1.24
Ω/1000ft at 75°C

Voltage Drop at 150 Feet

Single phase, copper conductor, one-way distance. ✅ = under 3%, ⚠️ = 3-5%, ❌ = over 5%

Load V-Drop @ 120V @ 240V
15A 5.6V ⚠️ 4.7% ✅ 2.3%
20A 7.4V ❌ 6.2% ⚠️ 3.1%
25A 9.3V ❌ 7.8% ⚠️ 3.9%
30A 11.2V ❌ 9.3% ⚠️ 4.7%

Maximum 10 AWG Run for 3% Drop

Longest one-way distance that keeps single-phase copper within 3%.

Load @ 120V @ 240V
15A 95 ft 195 ft
20A 75 ft 145 ft
25A 60 ft 115 ft
30A 50 ft 95 ft

How Voltage Drop Is Calculated

Voltage drop for single-phase circuits: Vdrop = 2 × I × R × L

Where I = current in amps, R = resistance per foot (0.00124 Ω/ft for 10 AWG copper, from NEC Chapter 9 Table 8 at 75°C), and L = one-way distance (150 ft).

The factor of 2 accounts for both the supply and return conductors. NEC recommends a maximum 3% voltage drop for branch circuits and 5% for the total circuit (feeder + branch).

If voltage drop is too high: Use the next larger wire size. Each single AWG step up in size cuts voltage drop by about 21% — it takes three steps to roughly halve it, since each step increases the conductor area by a factor of 1.26. Alternatively, for 120V loads, consider rewiring for 240V — same absolute drop but half the percentage.

Frequently Asked Questions

Can I use 10 AWG wire for a 150-foot run?

It depends on the load and voltage. With NEC Table 8 resistance (1.24 Ω per 1000 ft at 75°C), a 150-foot run of 10 AWG copper drops 4.7% at 15A, 6.2% at 20A, 7.8% at 25A, 9.3% at 30A on 120V, and half those percentages on 240V. At 240V, loads up to 15A meet the 3% guideline.

How far can you run 10 AWG wire?

To stay within 3% voltage drop, 10 AWG copper can run about 95 ft at 15A on 120V, or 95 ft at 30A on 240V (one-way). Its maximum load is 30A (the NEC 240.4(D) limit); lighter loads can run proportionally farther.

When should I upsize from 10 AWG over 150 feet?

Upsize when your load pushes drop above 3%. At 30A on 240V over 150 feet, 10 AWG drops 4.7%; stepping up to 8 AWG cuts that to 2.9%. For motors, well pumps or sensitive electronics, aim for 2% or less.