1/0 AWG Wire for 150 Feet

Voltage drop analysis for 1/0 AWG copper wire over a 150-foot one-way run. See whether this gauge is suitable for your circuit at various loads and voltages.

Wire
1/0 AWG
Distance
150 ft
Resistance
0.0983
Ω/1000ft

Voltage Drop at 150 Feet

Single phase, copper conductor, one-way distance. ✅ = under 3%, ⚠️ = 3-5%, ❌ = over 5%

Load V-Drop @ 120V @ 240V
15A 0.44V ✅ 0.4% ✅ 0.2%
20A 0.59V ✅ 0.5% ✅ 0.2%
30A 0.88V ✅ 0.7% ✅ 0.4%
40A 1.18V ✅ 1.0% ✅ 0.5%
50A 1.47V ✅ 1.2% ✅ 0.6%

How Voltage Drop Is Calculated

Voltage drop for single-phase circuits: Vdrop = 2 × I × R × L

Where I = current in amps, R = resistance per foot (0.000098 Ω/ft for 1/0 AWG copper), and L = one-way distance (150 ft).

The factor of 2 accounts for both the supply and return conductors. NEC recommends a maximum 3% voltage drop for branch circuits and 5% for the total circuit (feeder + branch).

If voltage drop is too high: Use the next larger wire size. Going from 1/0 to 2/0 AWG roughly halves the voltage drop. Alternatively, for 120V loads, consider rewiring for 240V — same absolute drop but half the percentage.