6 AWG Wire for 200 Feet

Voltage drop analysis for 6 AWG copper wire over a 200-foot one-way run. See whether this gauge is suitable for your circuit at various loads and voltages.

Wire
6 AWG
Distance
200 ft
Resistance
0.395
Ω/1000ft

Voltage Drop at 200 Feet

Single phase, copper conductor, one-way distance. ✅ = under 3%, ⚠️ = 3-5%, ❌ = over 5%

Load V-Drop @ 120V @ 240V
15A 2.37V ✅ 2.0% ✅ 1.0%
20A 3.16V ✅ 2.6% ✅ 1.3%
30A 4.74V ⚠️ 4.0% ✅ 2.0%
40A 6.32V ❌ 5.3% ✅ 2.6%
50A 7.9V ❌ 6.6% ⚠️ 3.3%

How Voltage Drop Is Calculated

Voltage drop for single-phase circuits: Vdrop = 2 × I × R × L

Where I = current in amps, R = resistance per foot (0.000395 Ω/ft for 6 AWG copper), and L = one-way distance (200 ft).

The factor of 2 accounts for both the supply and return conductors. NEC recommends a maximum 3% voltage drop for branch circuits and 5% for the total circuit (feeder + branch).

If voltage drop is too high: Use the next larger wire size. Going from 6 to 5 AWG roughly halves the voltage drop. Alternatively, for 120V loads, consider rewiring for 240V — same absolute drop but half the percentage.