6 AWG Wire for 25 Feet

Over 25 feet one-way, 6 AWG copper drops 0.6% at 30A on 120V and 0.6% at 60A on 240V: every load here up to 60A stays under 3% at 120V, and every load here up to 60A stays under 3% at 240V.

Wire
6 AWG
Distance
25 ft
Resistance
0.491
Ω/1000ft at 75°C

Voltage Drop at 25 Feet

Single phase, copper conductor, one-way distance. ✅ = under 3%, ⚠️ = 3-5%, ❌ = over 5%

Load V-Drop @ 120V @ 240V
30A 0.7V ✅ 0.6% ✅ 0.3%
40A 1.0V ✅ 0.8% ✅ 0.4%
50A 1.2V ✅ 1.0% ✅ 0.5%
60A* 1.5V ✅ 1.2% ✅ 0.6%

Maximum 6 AWG Run for 3% Drop

Longest one-way distance that keeps single-phase copper within 3%.

Load @ 120V @ 240V
30A 120 ft 245 ft
40A 90 ft 185 ft
50A 75 ft 145 ft
60A 60 ft 120 ft

* Above 55A, 6 AWG needs 75°C-rated terminations at both ends (NEC 110.14(C)); most breakers and panels rated 100A or less assume 60°C unless marked 75°C.

How Voltage Drop Is Calculated

Voltage drop for single-phase circuits: Vdrop = 2 × I × R × L

Where I = current in amps, R = resistance per foot (0.000491 Ω/ft for 6 AWG copper, from NEC Chapter 9 Table 8 at 75°C), and L = one-way distance (25 ft).

The factor of 2 accounts for both the supply and return conductors. NEC recommends a maximum 3% voltage drop for branch circuits and 5% for the total circuit (feeder + branch).

If voltage drop is too high: Use the next larger wire size. Each single AWG step up in size cuts voltage drop by about 21% — it takes three steps to roughly halve it, since each step increases the conductor area by a factor of 1.26. Alternatively, for 120V loads, consider rewiring for 240V — same absolute drop but half the percentage.

Frequently Asked Questions

Can I use 6 AWG wire for a 25-foot run?

It depends on the load and voltage. With NEC Table 8 resistance (0.491 Ω per 1000 ft at 75°C), a 25-foot run of 6 AWG copper drops 0.6% at 30A, 0.8% at 40A, 1.0% at 50A, 1.2% at 60A on 120V, and half those percentages on 240V. All of these meet the 3% branch-circuit guideline at 240V.

How far can you run 6 AWG wire?

To stay within 3% voltage drop, 6 AWG copper can run about 120 ft at 30A on 120V, or 120 ft at 60A on 240V (one-way). Its maximum load is 65A at 75°C; lighter loads can run proportionally farther.

When should I upsize from 6 AWG over 25 feet?

Upsize when your load pushes drop above 3%. At 60A on 240V over 25 feet, 6 AWG drops 0.6%; stepping up to 4 AWG cuts that to 0.4%. For motors, well pumps or sensitive electronics, aim for 2% or less.

Other distances for 6 AWG

Other gauges at 25 feet

Related

Voltage drop formula → 6 AWG full specifications → Wire size calculator → All distance charts →