WireSizing
Wire gauge reference & calculator

12 AWG Wire for 25 Feet

Voltage drop analysis for 12 AWG copper wire over a 25-foot one-way run. See whether this gauge is suitable for your circuit at various loads and voltages.

Wire
12 AWG
Distance
25 ft
Resistance
1.5881
Ω/1000ft

Voltage Drop at 25 Feet

Single phase, copper conductor, one-way distance. ✅ = under 3%, ⚠️ = 3-5%, ❌ = over 5%

Load V-Drop @ 120V @ 240V
15A 1.19V ✅ 1.0% ✅ 0.5%
20A 1.59V ✅ 1.3% ✅ 0.7%

How Voltage Drop Is Calculated

Voltage drop for single-phase circuits: Vdrop = 2 × I × R × L

Where I = current in amps, R = resistance per foot (0.001588 Ω/ft for 12 AWG copper), and L = one-way distance (25 ft).

The factor of 2 accounts for both the supply and return conductors. NEC recommends a maximum 3% voltage drop for branch circuits and 5% for the total circuit (feeder + branch).

If voltage drop is too high: Use the next larger wire size. Going from 12 to 11 AWG roughly halves the voltage drop. Alternatively, for 120V loads, consider rewiring for 240V — same absolute drop but half the percentage.

Related

12 AWG full specifications → Wire size calculator → All distance charts →