12 AWG Wire

12 AWG (American Wire Gauge) wire specifications: 2.0525 mm diameter, 3.3088 mm² area, 25A ampacity (copper, 75°C), protected at 20A max per NEC 240.4(D). Resistance, weight, and common uses.

Diameter
2.0525 mm
0.080808"
Area
3.3088 mm²
6,530 cmil
Ampacity (Cu)
25A
75°C · 20A breaker max
Resistance (Cu)
5.2104
Ω/km at 20°C
Breaker limit: 12 AWG copper is rated 25A at 75°C in NEC Table 310.16, but NEC 240.4(D) limits the overcurrent device to 20A (15A for 12 AWG aluminum). Size the breaker to 20A, not 25A. See wire size for 20 amps.

12 AWG — Complete Specifications

Diameter2.0525 mm · 0.080808" · 80.81 mils
Cross-sectional area3.3088 mm² · 6,530 circular mils
Resistance (copper, 20°C)5.2104 Ω/km · 1.5881 Ω/1000ft
Resistance (aluminum, 20°C)8.5417 Ω/km · 2.6035 Ω/1000ft
Ampacity — copper 60°C20 A
Ampacity — copper 75°C25 A
Ampacity — copper 90°C30 A
Ampacity — aluminum 75°C20 A
Weight (copper)29.647 kg/km · 19.922 lbs/1000ft
Weight (aluminum)8.934 kg/km · 6.003 lbs/1000ft
Closest IEC 60228 size4 mm²
Skin depth at 60 Hz8.531 mm

Common Uses for 12 AWG Wire

Compatible Insulation Types

TypeTemperatureDescription
THHN/THWN-2 90°C dry / 75°C wet Building wire
NM-B (Romex) 90°C Residential cable
MTW 60/90°C Machine tool wire
TFFN 90°C Fixture wire

Frequently Asked Questions

What is 12 AWG wire used for?

12 AWG copper is commonly used for 20A receptacle circuits, including kitchen, bathroom and garage outlets. NEC Table 310.16 rates it 25A at 75°C, but NEC 240.4(D) limits the breaker or fuse protecting it to 20A, which is why it is the standard wire for 20A circuits. It measures 2.053 mm in diameter with a 3.31 mm² cross-section.

What is the ampacity of 12 AWG wire?

Per NEC Table 310.16 (30°C ambient, no more than three current-carrying conductors), 12 AWG copper is rated 20A at 60°C, 25A at 75°C and 30A at 90°C. 12 AWG aluminum is rated 15A, 20A and 25A in the same columns. Regardless of those ratings, NEC 240.4(D) caps overcurrent protection at 20A for copper and 15A for aluminum. On circuits of 100A or less, NEC 110.14(C) generally requires the 60°C column unless every termination is rated 75°C.

Is 12 AWG wire available in aluminum?

Yes, but it is uncommon for new work. 12 AWG aluminum is rated 20A at 75°C, and NEC 240.4(D) limits it to a 15A breaker. Small-gauge aluminum branch wiring from the 1960s–70s is known for overheating at connections, so any device on it must be rated CO/ALR or AL/CU, or pigtailed with approved connectors.

12 AWG voltage drop by distance

Circuits that use 12 AWG copper

Explore

Conduit fill charts → Wire types and insulation ratings → Full AWG chart → Wire size calculator → AWG to mm² converter → Ampacity tables → Wire materials →