| Item | Value |
|---|---|
| Breaker type | Single-pole, 120 V |
| Recommended copper conductor | 12 AWG |
| Recommended aluminum conductor | 10 AWG |
| Minimum per NEC Table 310.16, 75°C | 14 AWG copper (20 A) |
| Minimum NM-B cable, 60°C column | 12 AWG copper (20 A) |
| Equipment grounding conductor | 12 AWG copper / 10 AWG aluminum (NEC Table 250.122) |
| Maximum continuous load (125% rule) | 16 A |
| Maximum non-continuous load | 20 A |
Kitchen small-appliance circuits, bathroom receptacles, laundry, garage and outdoor receptacles, workshop tools
| Load | Notes |
|---|---|
| Kitchen small-appliance circuits | Two required — NEC 210.52(B) |
| Bathroom receptacle circuit | Dedicated 20 A required — NEC 210.11(C)(3) |
| Laundry receptacle circuit | Dedicated 20 A required — NEC 210.11(C)(2) |
| Dishwasher | Commonly 15 A, often wired 20 A |
| Garbage disposal | Typically 15 A or 20 A |
| Microwave (built-in) | Dedicated 20 A circuit |
20 A on 12 AWG copper is the workhorse circuit of modern residential wiring. NEC 240.4(D)(5) caps 12 AWG copper at 20 A despite the 25 A figure in Table 310.16.
GFCI required for all kitchen countertop, bathroom, garage, outdoor, basement, and laundry receptacles (NEC 210.8(A)). AFCI required in most dwelling rooms (NEC 210.12(A)).
| One-way run | Drop | % of 120V | Verdict |
|---|---|---|---|
| 25 ft | 1.98 V | 1.6% | Within the 3% branch-circuit target |
| 50 ft | 3.96 V | 3.3% | Over 3% — upsize one gauge |
| 75 ft | 5.94 V | 4.9% | Over 3% — upsize one gauge |
| 100 ft | 7.92 V | 6.6% | Well over 3% — upsize two gauges or more |
| 150 ft | 11.88 V | 9.9% | Well over 3% — upsize two gauges or more |
| 200 ft | 15.84 V | 13.2% | Well over 3% — upsize two gauges or more |
The 80% rule: a continuous load is one expected to run for three hours or more — EV chargers, electric heat, and most commercial lighting. NEC 210.20(A) requires the overcurrent device to be rated at not less than 125% of that continuous load, which leaves 16 A usable on a 20 A breaker. A breaker that trips after an hour or two under a steady load is usually a continuous-load sizing mistake, not a faulty breaker.