WireSizing
Wire gauge reference & calculator

20 Amp Breaker Wire Size

Copper Wire
12 AWG
Aluminum Wire
10 AWG
Ground (Copper)
12 AWG
Single-pole · 120 V · Max continuous load 16 A · NEC Tables 310.16 and 250.122

20 Amp Circuit — Specification Summary

ItemValue
Breaker typeSingle-pole, 120 V
Recommended copper conductor12 AWG
Recommended aluminum conductor10 AWG
Minimum per NEC Table 310.16, 75°C12 AWG copper (25 A, limited to 20 A by NEC 240.4(D))
Minimum NM-B cable, 60°C column12 AWG copper (20 A)
Equipment grounding conductor12 AWG copper / 10 AWG aluminum (NEC Table 250.122)
Maximum continuous load (125% rule)16 A
Maximum non-continuous load20 A
The recommended conductor meets the 60°C column of NEC Table 310.16, so it works with NM-B cable and with any breaker or lug. NEC 110.14(C)(1)(a) requires the 60°C column at 100 A or less unless every termination is rated 75°C.

Common Uses for 20 A Circuits

Kitchen small-appliance circuits, bathroom receptacles, laundry, garage and outdoor receptacles, workshop tools

What a 20 Amp Breaker Powers

LoadNotes
Kitchen small-appliance circuitsTwo required — NEC 210.52(B)
Bathroom receptacle circuitDedicated 20 A required — NEC 210.11(C)(3)
Laundry receptacle circuitDedicated 20 A required — NEC 210.11(C)(2)
DishwasherCommonly 15 A, often wired 20 A
Garbage disposalTypically 15 A or 20 A
Microwave (built-in)Dedicated 20 A circuit
Always size a circuit from the equipment nameplate or a load calculation, not from a general table. Air conditioners and heat pumps in particular carry a minimum circuit ampacity (MCA) and maximum overcurrent protective device (MOCP) rating that override the general rules.

NEC requirements for this circuit

20 A on 12 AWG copper is the workhorse circuit of modern residential wiring. NEC 240.4(D)(5) caps 12 AWG copper at 20 A despite the 25 A figure in Table 310.16.

GFCI required for all kitchen countertop, bathroom, garage, outdoor, basement, and laundry receptacles (NEC 210.8(A)). AFCI required in most dwelling rooms (NEC 210.12(A)).

Voltage Drop by Distance — 12 AWG Copper at 20 A

One-way runDrop% of 120VVerdict
25 ft1.98 V1.6%Within the 3% branch-circuit target
50 ft3.96 V3.3%Over 3% — upsize one gauge
75 ft5.94 V4.9%Over 3% — upsize one gauge
100 ft7.92 V6.6%Well over 3% — upsize two gauges or more
150 ft11.88 V9.9%Well over 3% — upsize two gauges or more
200 ft15.84 V13.2%Well over 3% — upsize two gauges or more
Single-phase, 120V, full 20 A load, 1.98 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. See the voltage drop formula for the arithmetic.

The 80% rule: a continuous load is one expected to run for three hours or more — EV chargers, electric heat, and most commercial lighting. NEC 210.20(A) requires the overcurrent device to be rated at not less than 125% of that continuous load, which leaves 16 A usable on a 20 A breaker. A breaker that trips after an hour or two under a steady load is usually a continuous-load sizing mistake, not a faulty breaker.

Other Breaker Sizes

Frequently Asked Questions

What size wire do I need for a 20 amp breaker?

12 AWG copper or 10 AWG aluminum, per NEC Table 310.16 at the 75°C column. The equipment grounding conductor is 12 AWG copper per NEC Table 250.122.

What is the maximum continuous load on a 20 amp breaker?

16 amps. NEC 210.19(A)(1) and 210.20(A) require the circuit to be rated at 125% of a continuous load — one that runs for three hours or more — which works out to 80% of the breaker rating available for continuous use. Non-continuous loads may use the full 20 A.

What size ground wire for a 20 amp breaker?

12 AWG copper or 10 AWG aluminum, from NEC Table 250.122. The table lists maximum overcurrent device ratings, so you round up to the next listed row. If the circuit conductors are upsized for voltage drop, NEC 250.122(B) requires the ground to be upsized proportionally too.

Can I use 12 AWG NM-B cable on a 20 amp breaker?

Yes. NEC 334.80 requires NM-B ampacity to be taken from the 60°C column of Table 310.16, where 12 AWG copper is rated 20 A. That is why NM-B sometimes needs a larger conductor than THHN in conduit for the same breaker.

Related

Wire size for 20 amps — full page → 12 AWG full specifications → NEC Table 250.122 — ground wire size → NEC Table 310.16 — conductor ampacity → Wire size calculator →