WireSizing
Wire gauge reference & calculator

60 Amp Breaker Wire Size

Copper Wire
6 AWG
Aluminum Wire
4 AWG
Ground (Copper)
10 AWG
Double-pole · 240 V · Max continuous load 48 A · NEC Tables 310.16 and 250.122

60 Amp Circuit — Specification Summary

ItemValue
Breaker typeDouble-pole, 240 V
Recommended copper conductor6 AWG
Recommended aluminum conductor4 AWG
Minimum per NEC Table 310.16, 75°C6 AWG copper (65 A)
Minimum NM-B cable, 60°C column4 AWG copper (70 A)
Equipment grounding conductor10 AWG copper / 8 AWG aluminum (NEC Table 250.122)
Maximum continuous load (125% rule)48 A
Maximum non-continuous load60 A
Recommended conductor sizes follow the 75°C column of NEC Table 310.16, the column that matches the termination rating of virtually all modern breakers and lugs (NEC 110.14(C)).

Common Uses for 60 A Circuits

Sub-panels, tankless water heaters, large central air conditioning, 48 A Level 2 EV chargers, electric furnaces

What a 60 Amp Breaker Powers

LoadNotes
Detached garage or shop sub-panel60 A feeder is very common
Tankless electric water heaterOften two or three 60 A circuits
Level 2 EV charger (48 A)48 × 1.25 = 60 A circuit
Large central air conditionerCheck nameplate MOCP
Electric furnaceUsually multiple staged circuits
Always size a circuit from the equipment nameplate or a load calculation, not from a general table. Air conditioners and heat pumps in particular carry a minimum circuit ampacity (MCA) and maximum overcurrent protective device (MOCP) rating that override the general rules.

NEC requirements for this circuit

60 A is where the difference between wire types matters most. 6 AWG copper THHN on 75°C terminations gives 65 A and works. 6 AWG NM-B is limited to the 60°C column at 55 A and does not work — a 60 A circuit in NM-B cable needs 4 AWG.

Outdoor receptacle outlets up to 250 V and 50 A require GFCI under NEC 210.8. Sub-panel feeders themselves do not, but remember a sub-panel must have its neutral and ground bars separated, with four conductors in the feeder (NEC 250.32).

Voltage Drop by Distance — 6 AWG Copper at 60 A

One-way runDrop% of 240VVerdict
25 ft1.47 V0.6%Within the 3% branch-circuit target
50 ft2.95 V1.2%Within the 3% branch-circuit target
75 ft4.42 V1.8%Within the 3% branch-circuit target
100 ft5.89 V2.5%Within the 3% branch-circuit target
150 ft8.84 V3.7%Over 3% — upsize one gauge
200 ft11.78 V4.9%Over 3% — upsize one gauge
Single-phase, 240V, full 60 A load, 0.491 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. See the voltage drop formula for the arithmetic.

The 80% rule: a continuous load is one expected to run for three hours or more — EV chargers, electric heat, and most commercial lighting. NEC 210.20(A) requires the overcurrent device to be rated at not less than 125% of that continuous load, which leaves 48 A usable on a 60 A breaker. A breaker that trips after an hour or two under a steady load is usually a continuous-load sizing mistake, not a faulty breaker.

Other Breaker Sizes

Related

Wire size for 60 amps — full page → 6 AWG full specifications → NEC Table 250.122 — ground wire size → NEC Table 310.16 — conductor ampacity → Wire size calculator →