Sub-panels, large EV chargers, heavy equipment
| Diameter | 4.1154 mm (0.162023") |
| Area | 13.3018 mm² |
| Resistance at 20°C | 1.2961 Ω/km |
| Weight | 119.184 kg/km |
| Ampacity (75°C) | 65 A |
Important: For long wire runs, you may need to upsize the wire to compensate for voltage drop. NEC recommends keeping voltage drop under 3% for branch circuits. Use our voltage drop calculator to check.
| One-way run | Drop | % of 240V | Verdict |
|---|---|---|---|
| 25 ft | 1.19 V | 0.5% | Within the 3% branch-circuit target |
| 50 ft | 2.37 V | 1.0% | Within the 3% branch-circuit target |
| 75 ft | 3.55 V | 1.5% | Within the 3% branch-circuit target |
| 100 ft | 4.74 V | 2.0% | Within the 3% branch-circuit target |
| 150 ft | 7.11 V | 3.0% | Within the 3% branch-circuit target |
| 200 ft | 9.48 V | 4.0% | Over 3% — upsize one gauge |