WireSizing
Wire gauge reference & calculator

What Wire Size for 60 Amps?

Copper Wire
6 AWG
4.1154 mm · 13.3018 mm²
Aluminum Wire
4 AWG
5.1894 mm · 21.1506 mm²
Breaker: 60A · Based on NEC Table 310.16, 75°C column (needs 75°C-rated terminations)

60-Amp Wire Size by Termination Rating

RuleCopperAluminum
60°C column — NM-B cable, or any termination not marked 75°C4 AWG3 AWG
75°C column — THHN/THWN-2 with 75°C-rated breaker and lugs6 AWG4 AWG

Most breakers and panelboards rated 100A or less are listed 60/75°C, but NM-B cable is always limited to the 60°C column (NEC 334.80). When in doubt, use the 60°C answer.

Common Uses for 60A Circuits

Sub-panels, large EV chargers, heavy equipment

6 AWG Copper — Key Specs

Diameter4.1154 mm (0.162023")
Area13.3018 mm²
Resistance at 20°C1.2961 Ω/km
Weight119.184 kg/km
Ampacity (75°C)65 A

Important: For long wire runs, you may need to upsize the wire to compensate for voltage drop. NEC recommends keeping voltage drop under 3% for branch circuits. Use our voltage drop calculator to check.

Voltage Drop by Distance — 6 AWG Copper at 60A

One-way run Drop % of 240V Verdict
25 ft1.47 V0.6%Within the 3% branch-circuit target
50 ft2.95 V1.2%Within the 3% branch-circuit target
75 ft4.42 V1.8%Within the 3% branch-circuit target
100 ft5.89 V2.5%Within the 3% branch-circuit target
150 ft8.84 V3.7%Over 3% — upsize one gauge
200 ft11.78 V4.9%Over 3% — upsize one gauge
Single-phase, 240V, full 60A load, 0.491 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. Voltage drop is a performance recommendation, not a code requirement — but exceeding it causes dim lights, slow motor starts, and wasted energy.

Related Appliance Guides

Frequently Asked Questions

What wire size do I need for 60 amps?

Using the 60°C column of NEC Table 310.16, which NEC 110.14(C) requires by default for circuits of 100A or less and always for NM-B cable, a 60-amp circuit needs 4 AWG copper or 3 AWG aluminum. With THHN/THWN-2 conductors and breakers and lugs rated 75°C, 6 AWG copper or 4 AWG aluminum is permitted.

What breaker do I need for 60 amps?

A 60-amp circuit uses a 60A double-pole circuit breaker. The breaker protects the 6 AWG copper (or 4 AWG aluminum) wire from overload. Double-pole breakers are used for 240V circuits and occupy two slots in the panel.

What wire size for a 60-amp garage sub-panel?

A 60-amp garage sub-panel feeder uses 6 AWG copper or 4 AWG aluminum THHN/XHHW with 75°C terminations, or 4 AWG copper or 3 AWG aluminum if the 60°C column applies (NM-B cable or 60°C lugs). It supports a small workshop with lighting, outlets and one 240V tool circuit.

What is the difference between 50A and 60A circuits?

Wire size can differ. At 50A, 6 AWG copper works in either column (55A at 60°C). At 60A, 6 AWG copper is only enough with 75°C-rated terminations and THHN (65A); with NM-B or 60°C terminations you need 4 AWG copper (70A). 50A circuits typically feed ranges, hot tubs and EV chargers; 60A circuits feed sub-panels, larger welders and high-draw HVAC equipment.

Wire size for other amperages

Related

Wire types and insulation ratings → 60 amp breaker — wire, ground and load → NEC Table 250.122 — ground wire size → 6 AWG full specifications → Full AWG chart → Wire size calculator → Ampacity tables → EV charger wiring guide →