Large sub-panels, commercial equipment
| Diameter | 5.1894 mm (0.204307") |
| Area | 21.1506 mm² |
| Resistance at 20°C | 0.8151 Ω/km |
| Weight | 189.51 kg/km |
| Ampacity (75°C) | 85 A |
Important: For long wire runs, you may need to upsize the wire to compensate for voltage drop. NEC recommends keeping voltage drop under 3% for branch circuits. Use our voltage drop calculator to check.
| One-way run | Drop | % of 240V | Verdict |
|---|---|---|---|
| 25 ft | 0.87 V | 0.4% | Within the 3% branch-circuit target |
| 50 ft | 1.74 V | 0.7% | Within the 3% branch-circuit target |
| 75 ft | 2.61 V | 1.1% | Within the 3% branch-circuit target |
| 100 ft | 3.48 V | 1.4% | Within the 3% branch-circuit target |
| 150 ft | 5.22 V | 2.2% | Within the 3% branch-circuit target |
| 200 ft | 6.96 V | 2.9% | Within the 3% branch-circuit target |
Aluminum carries about 61% of the current of copper for the same cross-section, so a 70A feeder that takes 4 AWG copper needs 3 AWG aluminum — typically one to two gauge sizes larger.
| Aluminum conductor | 3 AWG |
| Ampacity (75°C, Table 310.16) | 75 A |
| Copper equivalent | 4 AWG (85 A) |
| Resistance | 0.3029 Ω/1000 ft |
| Voltage drop at 100 ft, 70A | 4.24 V (1.8% of 240V) |