What Wire Size for 70 Amps?

Copper Wire
4 AWG
5.1894 mm · 21.1506 mm²
Aluminum Wire
3 AWG
5.8273 mm · 26.6705 mm²
Breaker: 70A · Based on NEC Table 310.16 (75°C insulation)

Common Uses for 70A Circuits

Large sub-panels, commercial equipment

4 AWG Copper — Key Specs

Diameter5.1894 mm (0.204307")
Area21.1506 mm²
Resistance at 20°C0.8151 Ω/km
Weight189.51 kg/km
Ampacity (75°C)85 A

Important: For long wire runs, you may need to upsize the wire to compensate for voltage drop. NEC recommends keeping voltage drop under 3% for branch circuits. Use our voltage drop calculator to check.

Voltage Drop by Distance — 4 AWG Copper at 70A

One-way run Drop % of 240V Verdict
25 ft0.87 V0.4%Within the 3% branch-circuit target
50 ft1.74 V0.7%Within the 3% branch-circuit target
75 ft2.61 V1.1%Within the 3% branch-circuit target
100 ft3.48 V1.4%Within the 3% branch-circuit target
150 ft5.22 V2.2%Within the 3% branch-circuit target
200 ft6.96 V2.9%Within the 3% branch-circuit target
Single-phase, 240V, full 70A load, 0.2484 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. Voltage drop is a performance recommendation, not a code requirement — but exceeding it causes dim lights, slow motor starts, and wasted energy.

Aluminum Feeder Specifications

Aluminum carries about 61% of the current of copper for the same cross-section, so a 70A feeder that takes 4 AWG copper needs 3 AWG aluminum — typically one to two gauge sizes larger.

Aluminum conductor3 AWG
Ampacity (75°C, Table 310.16)75 A
Copper equivalent4 AWG (85 A)
Resistance0.3029 Ω/1000 ft
Voltage drop at 100 ft, 70A4.24 V (1.8% of 240V)

Installing aluminum correctly

  • Modern aluminum building wire must be AA-8000 series alloy (NEC 310.14(A)(1)). The 1960s-era AA-1350 alloy behind aluminum’s bad reputation is no longer permitted for branch circuits.
  • Terminate only on lugs and breakers marked AL/CU or AL9CU. Copper-only terminals are the most common failure point.
  • Apply an antioxidant compound to the stripped conductor before landing it, unless the termination is listed as not requiring it.
  • Torque every connection to the manufacturer’s value with a calibrated torque tool — NEC 110.14(D) makes this mandatory. Loose aluminum terminations are the primary cause of feeder failures.
  • Aluminum runs roughly half the weight and a third to half the cost of copper at feeder sizes, which is why it dominates service entrance and sub-panel feeders.

Related

Circuit breaker size chart → Wire types and insulation ratings → NEC Table 250.122 — ground wire size → 4 AWG full specifications → Full AWG chart → Wire size calculator → Ampacity tables →