What Wire Size for 50 Amps?

Copper Wire
6 AWG
4.1154 mm · 13.3018 mm²
Aluminum Wire
4 AWG
5.1894 mm · 21.1506 mm²
Breaker: 50A · Based on NEC Table 310.16 (75°C insulation)

Common Uses for 50A Circuits

Ranges, hot tubs, EV chargers, sub-panels

6 AWG Copper — Key Specs

Diameter4.1154 mm (0.162023")
Area13.3018 mm²
Resistance at 20°C1.2961 Ω/km
Weight119.184 kg/km
Ampacity (75°C)65 A

Important: For long wire runs, you may need to upsize the wire to compensate for voltage drop. NEC recommends keeping voltage drop under 3% for branch circuits. Use our voltage drop calculator to check.

Voltage Drop by Distance — 6 AWG Copper at 50A

One-way run Drop % of 240V Verdict
25 ft0.99 V0.4%Within the 3% branch-circuit target
50 ft1.98 V0.8%Within the 3% branch-circuit target
75 ft2.96 V1.2%Within the 3% branch-circuit target
100 ft3.95 V1.6%Within the 3% branch-circuit target
150 ft5.92 V2.5%Within the 3% branch-circuit target
200 ft7.90 V3.3%Over 3% — upsize one gauge
Single-phase, 240V, full 50A load, 0.395 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. Voltage drop is a performance recommendation, not a code requirement — but exceeding it causes dim lights, slow motor starts, and wasted energy.

Related Appliance Guides

Related

Wire types and insulation ratings → 50 amp breaker — wire, ground and load → NEC Table 250.122 — ground wire size → 6 AWG full specifications → Full AWG chart → Wire size calculator → Ampacity tables →