Ranges, hot tubs, EV chargers, sub-panels
| Diameter | 4.1154 mm (0.162023") |
| Area | 13.3018 mm² |
| Resistance at 20°C | 1.2961 Ω/km |
| Weight | 119.184 kg/km |
| Ampacity (75°C) | 65 A |
Important: For long wire runs, you may need to upsize the wire to compensate for voltage drop. NEC recommends keeping voltage drop under 3% for branch circuits. Use our voltage drop calculator to check.
| One-way run | Drop | % of 240V | Verdict |
|---|---|---|---|
| 25 ft | 0.99 V | 0.4% | Within the 3% branch-circuit target |
| 50 ft | 1.98 V | 0.8% | Within the 3% branch-circuit target |
| 75 ft | 2.96 V | 1.2% | Within the 3% branch-circuit target |
| 100 ft | 3.95 V | 1.6% | Within the 3% branch-circuit target |
| 150 ft | 5.92 V | 2.5% | Within the 3% branch-circuit target |
| 200 ft | 7.90 V | 3.3% | Over 3% — upsize one gauge |