WireSizing
Wire gauge reference & calculator

What Wire Size for 50 Amps?

Copper Wire
6 AWG
4.1154 mm · 13.3018 mm²
Aluminum Wire
4 AWG
5.1894 mm · 21.1506 mm²
Breaker: 50A · Based on NEC Table 310.16, 60°C column (the NEC 110.14(C) default at 100A or less)

50-Amp Wire Size by Termination Rating

RuleCopperAluminum
60°C column — NM-B cable, or any termination not marked 75°C6 AWG4 AWG
75°C column — THHN/THWN-2 with 75°C-rated breaker and lugs8 AWG6 AWG

Most breakers and panelboards rated 100A or less are listed 60/75°C, but NM-B cable is always limited to the 60°C column (NEC 334.80). When in doubt, use the 60°C answer.

Common Uses for 50A Circuits

Ranges, hot tubs, EV chargers, sub-panels

6 AWG Copper — Key Specs

Diameter4.1154 mm (0.162023")
Area13.3018 mm²
Resistance at 20°C1.2961 Ω/km
Weight119.184 kg/km
Ampacity (75°C)65 A

Important: For long wire runs, you may need to upsize the wire to compensate for voltage drop. NEC recommends keeping voltage drop under 3% for branch circuits. Use our voltage drop calculator to check.

Voltage Drop by Distance — 6 AWG Copper at 50A

One-way run Drop % of 240V Verdict
25 ft1.23 V0.5%Within the 3% branch-circuit target
50 ft2.46 V1.0%Within the 3% branch-circuit target
75 ft3.68 V1.5%Within the 3% branch-circuit target
100 ft4.91 V2.0%Within the 3% branch-circuit target
150 ft7.37 V3.1%Over 3% — upsize one gauge
200 ft9.82 V4.1%Over 3% — upsize one gauge
Single-phase, 240V, full 50A load, 0.491 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. Voltage drop is a performance recommendation, not a code requirement — but exceeding it causes dim lights, slow motor starts, and wasted energy.

Related Appliance Guides

Frequently Asked Questions

What wire size do I need for 50 amps?

Using the 60°C column of NEC Table 310.16, which NEC 110.14(C) requires by default for circuits of 100A or less and always for NM-B cable, a 50-amp circuit needs 6 AWG copper or 4 AWG aluminum. With THHN/THWN-2 conductors and breakers and lugs rated 75°C, 8 AWG copper or 6 AWG aluminum is permitted.

What breaker do I need for 50 amps?

A 50-amp circuit uses a 50A double-pole circuit breaker. The breaker protects the 6 AWG copper (or 4 AWG aluminum) wire from overload. Double-pole breakers are used for 240V circuits and occupy two slots in the panel.

What wire size for a hot tub on a 50-amp circuit?

A 50-amp hot tub circuit requires 6 AWG copper or 4 AWG aluminum wire on a 50A GFCI double-pole breaker. NEC 680.44 requires GFCI protection for hot tub feeders. The disconnect must be within sight of the spa, 5–50 feet away.

What wire size for a Level 2 EV charger?

EV chargers are continuous loads, so the circuit must be rated at 125% of the charger current (NEC 625.41). A 40A charger needs a 50A circuit: 6 AWG copper in NM-B, or 8 AWG THHN with 75°C terminations. A 48A charger needs a 60A circuit: 6 AWG THHN with 75°C terminations, or 4 AWG copper if the 60°C column applies (including NM-B).

Wire size for other amperages

Related

Wire types and insulation ratings → 50 amp breaker — wire, ground and load → NEC Table 250.122 — ground wire size → 6 AWG full specifications → Full AWG chart → Wire size calculator → Ampacity tables → EV charger wiring guide →