WireSizing
Wire gauge reference & calculator

50 Amp Breaker Wire Size

Copper Wire
6 AWG
Aluminum Wire
4 AWG
Ground (Copper)
10 AWG
Double-pole · 240 V · Max continuous load 40 A · NEC Tables 310.16 and 250.122

50 Amp Circuit — Specification Summary

ItemValue
Breaker typeDouble-pole, 240 V
Recommended copper conductor6 AWG
Recommended aluminum conductor4 AWG
Minimum per NEC Table 310.16, 75°C8 AWG copper (50 A)
Minimum NM-B cable, 60°C column6 AWG copper (55 A)
Equipment grounding conductor10 AWG copper / 8 AWG aluminum (NEC Table 250.122)
Maximum continuous load (125% rule)40 A
Maximum non-continuous load50 A
Recommended conductor sizes follow the 75°C column of NEC Table 310.16, the column that matches the termination rating of virtually all modern breakers and lugs (NEC 110.14(C)).

Common Uses for 50 A Circuits

Electric ranges, hot tubs and spas, 40 A Level 2 EV chargers, welders, sub-panels

What a 50 Amp Breaker Powers

LoadNotes
Electric range (freestanding)50 A is the standard range circuit
Hot tub / spaGFCI required — NEC 680.44
Level 2 EV charger (40 A)40 × 1.25 = 50 A circuit
WelderSized under NEC 630.11 by duty cycle
Garage or shop sub-panel50 A feeder
Always size a circuit from the equipment nameplate or a load calculation, not from a general table. Air conditioners and heat pumps in particular carry a minimum circuit ampacity (MCA) and maximum overcurrent protective device (MOCP) rating that override the general rules.

NEC requirements for this circuit

The 50 A circuit is the most common large residential circuit. Note that 6 AWG NM-B (Romex) is rated from the 60°C column at 55 A, so it is legal here — but 6 AWG NM-B is not permitted on a 60 A breaker.

Hot tubs and spas require GFCI protection on the feeder under NEC 680.44, with a disconnect within sight and between 5 and 50 feet from the water. EV charging equipment has built-in ground-fault protection but the receptacle version still requires GFCI under NEC 210.8(A).

Voltage Drop by Distance — 6 AWG Copper at 50 A

One-way runDrop% of 240VVerdict
25 ft1.23 V0.5%Within the 3% branch-circuit target
50 ft2.46 V1.0%Within the 3% branch-circuit target
75 ft3.68 V1.5%Within the 3% branch-circuit target
100 ft4.91 V2.0%Within the 3% branch-circuit target
150 ft7.36 V3.1%Over 3% — upsize one gauge
200 ft9.82 V4.1%Over 3% — upsize one gauge
Single-phase, 240V, full 50 A load, 0.491 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. See the voltage drop formula for the arithmetic.

The 80% rule: a continuous load is one expected to run for three hours or more — EV chargers, electric heat, and most commercial lighting. NEC 210.20(A) requires the overcurrent device to be rated at not less than 125% of that continuous load, which leaves 40 A usable on a 50 A breaker. A breaker that trips after an hour or two under a steady load is usually a continuous-load sizing mistake, not a faulty breaker.

Other Breaker Sizes

Related

Wire size for 50 amps — full page → 6 AWG full specifications → NEC Table 250.122 — ground wire size → NEC Table 310.16 — conductor ampacity → Wire size calculator →