WireSizing
Wire gauge reference & calculator

100 Amp Breaker Wire Size

Copper Wire
1 AWG
Aluminum Wire
1/0 AWG
Ground (Copper)
8 AWG
Double-pole · 240 V · Max continuous load 80 A · NEC Tables 310.16 and 250.122

100 Amp Circuit — Specification Summary

ItemValue
Breaker typeDouble-pole, 240 V
Recommended copper conductor1 AWG
Recommended aluminum conductor1/0 AWG
Minimum per NEC Table 310.16, 75°C3 AWG copper (100 A)
Minimum NM-B cable, 60°C column1 AWG copper (110 A)
Equipment grounding conductor8 AWG copper / 6 AWG aluminum (NEC Table 250.122)
Maximum continuous load (125% rule)80 A
Maximum non-continuous load100 A
Recommended conductor sizes follow the 75°C column of NEC Table 310.16, the column that matches the termination rating of virtually all modern breakers and lugs (NEC 110.14(C)).

Common Uses for 100 A Circuits

Main service for a small home, detached garage and ADU feeders, large workshop sub-panels

What a 100 Amp Breaker Powers

LoadNotes
Detached garage / workshop sub-panelVery common 100 A feeder
Accessory dwelling unitFeeder sized from a load calculation
Small home main serviceThe old residential standard
Large shop equipment panelMultiple 240 V machines
Always size a circuit from the equipment nameplate or a load calculation, not from a general table. Air conditioners and heat pumps in particular carry a minimum circuit ampacity (MCA) and maximum overcurrent protective device (MOCP) rating that override the general rules.

NEC requirements for this circuit

At 100 A the choice of conductor depends on what the circuit is. A general feeder is sized from Table 310.16, where 3 AWG copper reaches exactly 100 A at 75°C. For a dwelling service, or a feeder carrying the entire load of a dwelling, NEC 310.12 permits 83% sizing — which is why 4 AWG copper or 2 AWG aluminum is accepted for a 100 A house service. 1 AWG copper is the conservative choice that covers either case with margin for voltage drop.

Feeders do not require GFCI. A 100 A feeder to a separate structure must include an equipment grounding conductor and requires a grounding electrode system at the structure (NEC 250.32(A)), with neutral and ground kept separate in the sub-panel.

Voltage Drop by Distance — 1 AWG Copper at 100 A

One-way runDrop% of 240VVerdict
25 ft0.77 V0.3%Within the 3% branch-circuit target
50 ft1.54 V0.6%Within the 3% branch-circuit target
75 ft2.31 V1.0%Within the 3% branch-circuit target
100 ft3.08 V1.3%Within the 3% branch-circuit target
150 ft4.62 V1.9%Within the 3% branch-circuit target
200 ft6.16 V2.6%Within the 3% branch-circuit target
Single-phase, 240V, full 100 A load, 0.154 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. See the voltage drop formula for the arithmetic.

The 80% rule: a continuous load is one expected to run for three hours or more — EV chargers, electric heat, and most commercial lighting. NEC 210.20(A) requires the overcurrent device to be rated at not less than 125% of that continuous load, which leaves 80 A usable on a 100 A breaker. A breaker that trips after an hour or two under a steady load is usually a continuous-load sizing mistake, not a faulty breaker.

Other Breaker Sizes

Related

Wire size for 100 amps — full page → 1 AWG full specifications → NEC Table 250.122 — ground wire size → NEC Table 310.16 — conductor ampacity → Wire size calculator →