| Item | Value |
|---|---|
| Breaker type | Double-pole, 240 V |
| Recommended copper conductor | 1 AWG |
| Recommended aluminum conductor | 1/0 AWG |
| Minimum per NEC Table 310.16, 75°C | 3 AWG copper (100 A) |
| Minimum NM-B cable, 60°C column | 1 AWG copper (110 A) |
| Equipment grounding conductor | 8 AWG copper / 6 AWG aluminum (NEC Table 250.122) |
| Maximum continuous load (125% rule) | 80 A |
| Maximum non-continuous load | 100 A |
Main service for a small home, detached garage and ADU feeders, large workshop sub-panels
| Load | Notes |
|---|---|
| Detached garage / workshop sub-panel | Very common 100 A feeder |
| Accessory dwelling unit | Feeder sized from a load calculation |
| Small home main service | The old residential standard |
| Large shop equipment panel | Multiple 240 V machines |
At 100 A the choice of conductor depends on what the circuit is. A general feeder is sized from Table 310.16, where 3 AWG copper reaches exactly 100 A at 75°C. For a dwelling service, or a feeder carrying the entire load of a dwelling, NEC 310.12 permits 83% sizing — which is why 4 AWG copper or 2 AWG aluminum is accepted for a 100 A house service. 1 AWG copper is the conservative choice that covers either case with margin for voltage drop.
Feeders do not require GFCI. A 100 A feeder to a separate structure must include an equipment grounding conductor and requires a grounding electrode system at the structure (NEC 250.32(A)), with neutral and ground kept separate in the sub-panel.
| One-way run | Drop | % of 240V | Verdict |
|---|---|---|---|
| 25 ft | 0.77 V | 0.3% | Within the 3% branch-circuit target |
| 50 ft | 1.54 V | 0.6% | Within the 3% branch-circuit target |
| 75 ft | 2.31 V | 1.0% | Within the 3% branch-circuit target |
| 100 ft | 3.08 V | 1.3% | Within the 3% branch-circuit target |
| 150 ft | 4.62 V | 1.9% | Within the 3% branch-circuit target |
| 200 ft | 6.16 V | 2.6% | Within the 3% branch-circuit target |
The 80% rule: a continuous load is one expected to run for three hours or more — EV chargers, electric heat, and most commercial lighting. NEC 210.20(A) requires the overcurrent device to be rated at not less than 125% of that continuous load, which leaves 80 A usable on a 100 A breaker. A breaker that trips after an hour or two under a steady load is usually a continuous-load sizing mistake, not a faulty breaker.