30 Amp Breaker Wire Size

Copper Wire
10 AWG
Aluminum Wire
8 AWG
Ground (Copper)
10 AWG
Double-pole (or single-pole at 120 V) · 240 V or 120 V · Max continuous load 24 A · NEC Tables 310.16 and 250.122

30 Amp Circuit — Specification Summary

ItemValue
Breaker typeDouble-pole (or single-pole at 120 V), 240 V or 120 V
Recommended copper conductor10 AWG
Recommended aluminum conductor8 AWG
Minimum per NEC Table 310.16, 75°C10 AWG copper (35 A)
Minimum NM-B cable, 60°C column10 AWG copper (30 A)
Equipment grounding conductor10 AWG copper / 8 AWG aluminum (NEC Table 250.122)
Maximum continuous load (125% rule)24 A
Maximum non-continuous load30 A
Recommended conductor sizes follow the 75°C column of NEC Table 310.16, the column that matches the termination rating of virtually all modern breakers and lugs (NEC 110.14(C)).

Common Uses for 30 A Circuits

Electric clothes dryers, small water heaters, RV outlets, window and through-wall air conditioners, small sub-panels

What a 30 Amp Breaker Powers

LoadNotes
Electric clothes dryer4-wire 240 V, NEC 250.140
Water heater (small / point of use)240 V, continuous load
RV receptacle (TT-30)120 V, 30 A, NEC 551.71
Window air conditioner (large)240 V
Small sub-panelFeeder to a shed or shop
Always size a circuit from the equipment nameplate or a load calculation, not from a general table. Air conditioners and heat pumps in particular carry a minimum circuit ampacity (MCA) and maximum overcurrent protective device (MOCP) rating that override the general rules.

NEC requirements for this circuit

NEC 240.4(D)(7) caps 10 AWG copper at 30 A. A 30 A circuit is the largest that still falls under the small-conductor rule, so above 30 A Table 310.16 governs directly.

GFCI required for 30 A receptacle outlets in dwelling garages, outdoors, basements and similar locations under NEC 210.8, which now covers receptacles up to 250 V. Dryers hard-wired or on a 30 A outlet in a laundry room are covered by 210.8(A)(10) in the 2020 and later NEC.

Voltage Drop by Distance — 10 AWG Copper at 30 A

One-way runDrop% of 240VVerdict
25 ft1.86 V0.8%Within the 3% branch-circuit target
50 ft3.72 V1.5%Within the 3% branch-circuit target
75 ft5.58 V2.3%Within the 3% branch-circuit target
100 ft7.44 V3.1%Over 3% — upsize one gauge
150 ft11.16 V4.6%Over 3% — upsize one gauge
200 ft14.88 V6.2%Well over 3% — upsize two gauges or more
Single-phase, 240V, full 30 A load, 1.24 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. See the voltage drop formula for the arithmetic.

The 80% rule: a continuous load is one expected to run for three hours or more — EV chargers, electric heat, and most commercial lighting. NEC 210.20(A) requires the overcurrent device to be rated at not less than 125% of that continuous load, which leaves 24 A usable on a 30 A breaker. A breaker that trips after an hour or two under a steady load is usually a continuous-load sizing mistake, not a faulty breaker.