WireSizing
Wire gauge reference & calculator

NEC Table 310.16 — Conductor Ampacity

NEC Table 310.16 gives the allowable ampacity of insulated conductors rated up to 2000 volts, at not more than three current-carrying conductors in a raceway, cable, or earth, in a 30°C (86°F) ambient. It is the table every branch circuit and feeder in a building starts from. The headline numbers most people need: 14 AWG copper = 20 A, 12 AWG = 25 A, 10 AWG = 35 A at 75°C — but NEC 240.4(D) caps those same conductors at 15 A, 20 A and 30 A of overcurrent protection.

Table 310.16 — Copper Conductors

Size (AWG/kcmil)60°C (TW, UF)75°C (THW, THWN, XHHW)90°C (THHN, THWN-2, XHHW-2)
1415 A20 A25 A
1220 A25 A30 A
1030 A35 A40 A
840 A50 A55 A
655 A65 A75 A
470 A85 A95 A
385 A100 A115 A
295 A115 A130 A
1110 A130 A145 A
1/0125 A150 A170 A
2/0145 A175 A195 A
3/0165 A200 A225 A
4/0195 A230 A260 A
250 kcmil215 A255 A290 A
300 kcmil240 A285 A320 A
350 kcmil260 A310 A350 A
400 kcmil280 A335 A380 A
500 kcmil320 A380 A430 A
Ampacities in amperes. Based on ambient 30°C with not more than three current-carrying conductors. Correct for other ambients and conductor counts using Table 310.15.

Table 310.16 — Aluminum and Copper-Clad Aluminum Conductors

Size (AWG/kcmil)60°C (TW, UF)75°C (THW, THWN, XHHW)90°C (THHN, THWN-2, XHHW-2)
1215 A20 A25 A
1025 A30 A35 A
835 A40 A45 A
640 A50 A55 A
455 A65 A75 A
365 A75 A85 A
275 A90 A100 A
185 A100 A115 A
1/0100 A120 A135 A
2/0115 A135 A150 A
3/0130 A155 A175 A
4/0150 A180 A205 A
250 kcmil170 A205 A230 A
300 kcmil195 A230 A260 A
350 kcmil210 A250 A280 A
400 kcmil225 A270 A305 A
500 kcmil260 A310 A350 A
Aluminum starts at 12 AWG; 14 AWG aluminum is not a recognised building conductor. Aluminum needs roughly two gauge sizes more than copper for the same ampacity.

The 90°C column is almost never the answer

This is where most Table 310.16 mistakes happen. You may use the 90°C column as the starting point for derating calculations, but the final ampacity is limited by the temperature rating of the terminations at both ends of the circuit. NEC 110.14(C) puts most equipment at 60°C for circuits up to 100 A and 75°C above that, and virtually every breaker and lug in a residential or light commercial panel is listed 75°C.

In practice: 12 AWG THHN is a 90°C conductor, so you start derating from 30 A. But you land on a 75°C-rated breaker, so the answer can never exceed the 25 A in the 75°C column — and NEC 240.4(D) then caps the breaker at 20 A regardless. The 90°C column buys you derating headroom, not a bigger breaker.

NEC 240.4(D) overrides the table for small conductors

For 14, 12 and 10 AWG copper and 12 and 10 AWG aluminum, NEC 240.4(D) sets a hard limit on the overcurrent device that is lower than the Table 310.16 ampacity. This is not a suggestion or a rounding rule — it is the reason a 12 AWG circuit is a 20 A circuit even though the table says 25 A.

14 AWG copper: 15 A. 12 AWG copper: 20 A. 10 AWG copper: 30 A. 12 AWG aluminum: 15 A. 10 AWG aluminum: 25 A. 16 AWG copper: 10 A. 18 AWG copper: 7 A. Above 10 AWG the rule stops applying and Table 310.16 governs directly. NEC 240.4(E) and 240.4(G) list the exceptions — tap conductors, motor circuits, welders and similar loads sized under their own articles.

Our wire size calculator applies the 240.4(D) cap automatically.

Dwelling services get their own table

NEC 310.12 permits smaller conductors for a single-phase dwelling service or feeder carrying the entire load: the service conductors may be sized at 83% of the service rating. That is why a 200 A residential service is commonly wired with 2/0 copper or 4/0 aluminum rather than the 4/0 copper that Table 310.16 alone would demand. The 83% rule applies only to the main service or a feeder supplying the whole dwelling, never to ordinary branch circuits.

Related

Full ampacity tables →Wire size by amps →NEC Table 310.15 — correction and adjustment factors →Circuit breaker size charts →Wire size calculator →