WireSizing
Wire gauge reference & calculator

15 Amp Breaker Wire Size

Copper Wire
14 AWG
Aluminum Wire
12 AWG
Ground (Copper)
14 AWG
Single-pole · 120 V · Max continuous load 12 A · NEC Tables 310.16 and 250.122

15 Amp Circuit — Specification Summary

ItemValue
Breaker typeSingle-pole, 120 V
Recommended copper conductor14 AWG
Recommended aluminum conductor12 AWG
Minimum per NEC Table 310.16, 75°C14 AWG copper (20 A)
Minimum NM-B cable, 60°C column14 AWG copper (15 A)
Equipment grounding conductor14 AWG copper / 12 AWG aluminum (NEC Table 250.122)
Maximum continuous load (125% rule)12 A
Maximum non-continuous load15 A
Recommended conductor sizes follow the 75°C column of NEC Table 310.16, the column that matches the termination rating of virtually all modern breakers and lugs (NEC 110.14(C)).

Common Uses for 15 A Circuits

General lighting circuits, bedroom and living-room receptacles, smoke alarms, ceiling fans, garage door openers

What a 15 Amp Breaker Powers

LoadNotes
General lightingUp to 1440 W continuous
Bedroom receptaclesAFCI required — NEC 210.12
Smoke and CO alarmsOften on a dedicated 15 A circuit
Ceiling fans and light fixturesTypical whole-room circuit
Always size a circuit from the equipment nameplate or a load calculation, not from a general table. Air conditioners and heat pumps in particular carry a minimum circuit ampacity (MCA) and maximum overcurrent protective device (MOCP) rating that override the general rules.

NEC requirements for this circuit

15 A is the smallest standard branch circuit in a dwelling. NEC 240.4(D)(3) caps 14 AWG copper at 15 A even though Table 310.16 rates it 20 A at 75°C — this is why you can never legally put 14 AWG on a 20 A breaker.

GFCI required for receptacles in bathrooms, garages, outdoors, crawl spaces, unfinished basements, kitchens, laundry areas, and within 6 feet of any sink (NEC 210.8). AFCI required for most dwelling living areas (NEC 210.12).

Voltage Drop by Distance — 14 AWG Copper at 15 A

One-way runDrop% of 120VVerdict
25 ft2.35 V2.0%Within the 3% branch-circuit target
50 ft4.71 V3.9%Over 3% — upsize one gauge
75 ft7.07 V5.9%Well over 3% — upsize two gauges or more
100 ft9.42 V7.8%Well over 3% — upsize two gauges or more
150 ft14.13 V11.8%Well over 3% — upsize two gauges or more
200 ft18.84 V15.7%Well over 3% — upsize two gauges or more
Single-phase, 120V, full 15 A load, 3.14 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. See the voltage drop formula for the arithmetic.

The 80% rule: a continuous load is one expected to run for three hours or more — EV chargers, electric heat, and most commercial lighting. NEC 210.20(A) requires the overcurrent device to be rated at not less than 125% of that continuous load, which leaves 12 A usable on a 15 A breaker. A breaker that trips after an hour or two under a steady load is usually a continuous-load sizing mistake, not a faulty breaker.

Other Breaker Sizes

Related

Wire size for 15 amps — full page → 14 AWG full specifications → NEC Table 250.122 — ground wire size → NEC Table 310.16 — conductor ampacity → Wire size calculator →