| Item | Value |
|---|---|
| Breaker type | Single-pole, 120 V |
| Recommended copper conductor | 14 AWG |
| Recommended aluminum conductor | 12 AWG |
| Minimum per NEC Table 310.16, 75°C | 14 AWG copper (20 A) |
| Minimum NM-B cable, 60°C column | 14 AWG copper (15 A) |
| Equipment grounding conductor | 14 AWG copper / 12 AWG aluminum (NEC Table 250.122) |
| Maximum continuous load (125% rule) | 12 A |
| Maximum non-continuous load | 15 A |
General lighting circuits, bedroom and living-room receptacles, smoke alarms, ceiling fans, garage door openers
| Load | Notes |
|---|---|
| General lighting | Up to 1440 W continuous |
| Bedroom receptacles | AFCI required — NEC 210.12 |
| Smoke and CO alarms | Often on a dedicated 15 A circuit |
| Ceiling fans and light fixtures | Typical whole-room circuit |
15 A is the smallest standard branch circuit in a dwelling. NEC 240.4(D)(3) caps 14 AWG copper at 15 A even though Table 310.16 rates it 20 A at 75°C — this is why you can never legally put 14 AWG on a 20 A breaker.
GFCI required for receptacles in bathrooms, garages, outdoors, crawl spaces, unfinished basements, kitchens, laundry areas, and within 6 feet of any sink (NEC 210.8). AFCI required for most dwelling living areas (NEC 210.12).
| One-way run | Drop | % of 120V | Verdict |
|---|---|---|---|
| 25 ft | 2.35 V | 2.0% | Within the 3% branch-circuit target |
| 50 ft | 4.71 V | 3.9% | Over 3% — upsize one gauge |
| 75 ft | 7.07 V | 5.9% | Well over 3% — upsize two gauges or more |
| 100 ft | 9.42 V | 7.8% | Well over 3% — upsize two gauges or more |
| 150 ft | 14.13 V | 11.8% | Well over 3% — upsize two gauges or more |
| 200 ft | 18.84 V | 15.7% | Well over 3% — upsize two gauges or more |
The 80% rule: a continuous load is one expected to run for three hours or more — EV chargers, electric heat, and most commercial lighting. NEC 210.20(A) requires the overcurrent device to be rated at not less than 125% of that continuous load, which leaves 12 A usable on a 15 A breaker. A breaker that trips after an hour or two under a steady load is usually a continuous-load sizing mistake, not a faulty breaker.