WireSizing
Wire gauge reference & calculator

15 Amp Breaker Wire Size

Copper Wire
14 AWG
Aluminum Wire
12 AWG
Ground (Copper)
14 AWG
Single-pole · 120 V · Max continuous load 12 A · NEC Tables 310.16 and 250.122

15 Amp Circuit — Specification Summary

ItemValue
Breaker typeSingle-pole, 120 V
Recommended copper conductor14 AWG
Recommended aluminum conductor12 AWG
Minimum per NEC Table 310.16, 75°C14 AWG copper (20 A, limited to 15 A by NEC 240.4(D))
Minimum NM-B cable, 60°C column14 AWG copper (15 A)
Equipment grounding conductor14 AWG copper / 12 AWG aluminum (NEC Table 250.122)
Maximum continuous load (125% rule)12 A
Maximum non-continuous load15 A
The recommended conductor meets the 60°C column of NEC Table 310.16, so it works with NM-B cable and with any breaker or lug. NEC 110.14(C)(1)(a) requires the 60°C column at 100 A or less unless every termination is rated 75°C.

Common Uses for 15 A Circuits

General lighting circuits, bedroom and living-room receptacles, smoke alarms, ceiling fans, garage door openers

What a 15 Amp Breaker Powers

LoadNotes
General lightingUp to 1440 W continuous
Bedroom receptaclesAFCI required — NEC 210.12
Smoke and CO alarmsOften on a dedicated 15 A circuit
Ceiling fans and light fixturesTypical whole-room circuit
Always size a circuit from the equipment nameplate or a load calculation, not from a general table. Air conditioners and heat pumps in particular carry a minimum circuit ampacity (MCA) and maximum overcurrent protective device (MOCP) rating that override the general rules.

NEC requirements for this circuit

15 A is the smallest standard branch circuit in a dwelling. NEC 240.4(D)(3) caps 14 AWG copper at 15 A even though Table 310.16 rates it 20 A at 75°C — this is why you can never legally put 14 AWG on a 20 A breaker.

GFCI required for receptacles in bathrooms, garages, outdoors, crawl spaces, unfinished basements, kitchens, laundry areas, and within 6 feet of any sink (NEC 210.8). AFCI required for most dwelling living areas (NEC 210.12).

Voltage Drop by Distance — 14 AWG Copper at 15 A

One-way runDrop% of 120VVerdict
25 ft2.35 V2.0%Within the 3% branch-circuit target
50 ft4.71 V3.9%Over 3% — upsize one gauge
75 ft7.07 V5.9%Well over 3% — upsize two gauges or more
100 ft9.42 V7.8%Well over 3% — upsize two gauges or more
150 ft14.13 V11.8%Well over 3% — upsize two gauges or more
200 ft18.84 V15.7%Well over 3% — upsize two gauges or more
Single-phase, 120V, full 15 A load, 3.14 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. See the voltage drop formula for the arithmetic.

The 80% rule: a continuous load is one expected to run for three hours or more — EV chargers, electric heat, and most commercial lighting. NEC 210.20(A) requires the overcurrent device to be rated at not less than 125% of that continuous load, which leaves 12 A usable on a 15 A breaker. A breaker that trips after an hour or two under a steady load is usually a continuous-load sizing mistake, not a faulty breaker.

Other Breaker Sizes

Frequently Asked Questions

What size wire do I need for a 15 amp breaker?

14 AWG copper or 12 AWG aluminum, per NEC Table 310.16 at the 75°C column. The equipment grounding conductor is 14 AWG copper per NEC Table 250.122.

What is the maximum continuous load on a 15 amp breaker?

12 amps. NEC 210.19(A)(1) and 210.20(A) require the circuit to be rated at 125% of a continuous load — one that runs for three hours or more — which works out to 80% of the breaker rating available for continuous use. Non-continuous loads may use the full 15 A.

What size ground wire for a 15 amp breaker?

14 AWG copper or 12 AWG aluminum, from NEC Table 250.122. The table lists maximum overcurrent device ratings, so you round up to the next listed row. If the circuit conductors are upsized for voltage drop, NEC 250.122(B) requires the ground to be upsized proportionally too.

Can I use 14 AWG NM-B cable on a 15 amp breaker?

Yes. NEC 334.80 requires NM-B ampacity to be taken from the 60°C column of Table 310.16, where 14 AWG copper is rated 15 A. That is why NM-B sometimes needs a larger conductor than THHN in conduit for the same breaker.

Related

Wire size for 15 amps — full page → 14 AWG full specifications → NEC Table 250.122 — ground wire size → NEC Table 310.16 — conductor ampacity → Wire size calculator →